| Plan Review Notes For Permit 11040647 |
| Permit Number |
11040647 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2011-06-02 11:33:11 | BUILDING PROVISO: | | | BUILDING APPROVED WITH EXCEPTION! | | | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO | | | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO | | | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE | | | ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE | | | ADDITIONAL REVIEWS WITH ASSOCIATED FEES. | | | | | | 1) SHEET A-1 OCCUPANCY SEPERATION WALL (1 HOUR) BETWEEN | | | WAREHOUSE RESTROOM & BUSINESS/ MECANTILE SHOWROOM | | | MECHANICAL IS MISSING THE FIRE DAMPER PER : | | | 2007/09 FBC-B 716.1 GENERAL. THE PROVISIONS OF THIS | | | SECTION SHALL GOVERN THE PROTECTION OF DUCT | | | PENETRATIONS AND AIR TRANSFER OPENINGS IN ASSEMBLIES | | | REQUIRED TO BE PROTECTED. 716.3.1 FIRE PROTECTION | | | RATING. FIRE DAMPERS SHALL HAVE THE MINIMUM FIRE | | | PROTECTION RATING SPECIFIED IN TABLE 716.3.1 FOR THE | | | TYPE OF PENETRATION. | | | | | | 2ND REVIEW NO MECHANICAL SHEETS WERE SUBMITTED. |
|