2011-06-02 11:33:11BUILDING PROVISO:
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) SHEET A-1 OCCUPANCY SEPERATION WALL (1 HOUR) BETWEEN
 WAREHOUSE RESTROOM & BUSINESS/ MECANTILE SHOWROOM
 MECHANICAL IS MISSING THE FIRE DAMPER PER :
 2007/09 FBC-B 716.1 GENERAL. THE PROVISIONS OF THIS
 SECTION SHALL GOVERN THE PROTECTION OF DUCT
 PENETRATIONS AND AIR TRANSFER OPENINGS IN ASSEMBLIES
 REQUIRED TO BE PROTECTED. 716.3.1 FIRE PROTECTION
 RATING. FIRE DAMPERS SHALL HAVE THE MINIMUM FIRE
 PROTECTION RATING SPECIFIED IN TABLE 716.3.1 FOR THE
 TYPE OF PENETRATION.
  
 2ND REVIEW NO MECHANICAL SHEETS WERE SUBMITTED.