2011-05-11 11:20:49PLANS DENIED
 1) PROVIDE THE SIGNATURE AND LIC.NUMBER OF THE DESIGNER
 ON THE PLANS.
 2) REFER TO SECTION 106.1.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. 2007 FBC
 1) PROVIDE CFM ON ALL SUPPLY GRAILS. ON THE PLANS.
 2) PROVIDE MAKE UP AIR ON THE PLANS.
 3) PROVIDE BATHROOM VENTILATION ON THE PLANS.
 4) PROVIDE HANGING DETAIL FOR AIRHANDLERS ON THE PLANS.
 5) PROVIDE TIE DOWN DETAIL THE CONDENSER TO SLAB.ON
 PLANS.
 3) REFER TO SECTION 601.4 BALANCED RETURN AIR. 2007
 FBC(M)
 4) REFER TO SECTION 606.2.1 SUPPLY AIR. 2007 FBC (M)
 5) REFER TO SECTION 606.4.1 SUPERVISION. 2007 FBC (M)
 PLAN REVIEW BY HAROLD MOSER 561-805-6732
2011-05-11 10:42:27PLANS DENIED