| Permit Number |
11040647 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-05-11 11:20:49 | PLANS DENIED | | | 1) PROVIDE THE SIGNATURE AND LIC.NUMBER OF THE DESIGNER | | | ON THE PLANS. | | | 2) REFER TO SECTION 106.1.1 INFORMATION ON CONSTRUCTION | | | DOCUMENTS. 2007 FBC | | | 1) PROVIDE CFM ON ALL SUPPLY GRAILS. ON THE PLANS. | | | 2) PROVIDE MAKE UP AIR ON THE PLANS. | | | 3) PROVIDE BATHROOM VENTILATION ON THE PLANS. | | | 4) PROVIDE HANGING DETAIL FOR AIRHANDLERS ON THE PLANS. | | | 5) PROVIDE TIE DOWN DETAIL THE CONDENSER TO SLAB.ON | | | PLANS. | | | 3) REFER TO SECTION 601.4 BALANCED RETURN AIR. 2007 | | | FBC(M) | | | 4) REFER TO SECTION 606.2.1 SUPPLY AIR. 2007 FBC (M) | | | 5) REFER TO SECTION 606.4.1 SUPERVISION. 2007 FBC (M) | | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 | | 2011-05-11 10:42:27 | PLANS DENIED |
|