| Plan Review Notes For Permit 11040636 |
| Permit Number |
11040636 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-04-28 14:14:34 | FBC PLUMBING 2007 PLAN REVIEW #1 | | | DENIED: | | | | | | ***NOTE***FROM PAGE E-1 THE USE APPEARS TO BE | | | MERCANTILE- A SHOW ROOM FOR CONSTRUCTION FIXTURES. | | | | | | 1. SHEET A-5.1 THE WATER CLOSET IN THE NEW RESTROOM IS | | | REQUIRED TO BE 18" FROM SIDE WALL.11-4.16.2 CLEAR FLOOR | | | SPACE. CLEAR FLOOR SPACE FOR WATER CLOSETS NOT IN | | | STALLS SHALL COMPLY WITH FIGURE 28. CLEAR FLOOR SPACE | | | MAY BE ARRANGED TO ALLOW EITHER A LEFT-HANDED OR | | | RIGHT-HANDED APPROACH. | | | | | | 2. SHEET A-2.1 NEW PEDESTAL SINK MAY NOT COMPLY WITH | | | 11-4.19.2 HEIGHT AND CLEARANCES. LAVATORIES SHALL BE | | | MOUNTED WITH THE RIM OR COUNTER SURFACE NO HIGHER THAN | | | 34 INCHES (865 MM) ABOVE THE FINISH FLOOR. PROVIDE A | | | CLEARANCE OF AT LEAST 29 INCHES (735 MM) ABOVE THE | | | FINISH FLOOR TO THE BOTTOM OF THE APRON. KNEE AND TOE | | | CLEARANCE SHALL COMPLY WITH FIGURE 31. | | | | | | 3. SHEET A2.1 SINK CABINET SHOWN IS REQUIRED TO BE 34" | | | AFF MAX. 11-4.24.2 HEIGHT. SINKS SHALL BE MOUNTED WITH | | | THE COUNTER OR RIM NO HIGHER THAN 34 INCHES (865 MM) | | | ABOVE THE FINISH FLOOR. | | | | | | 4. BUSINESS AND MERCANTILE REQUIRE A DRINKING FOUNTAIN | | | TO BE INSTALLED. 403.1 MINIMUM NUMBER OF FIXTURES. | | | | | | 5. SANITARY, AND HOT AND COLD WATER ISOMETRIC WILL BE | | | REQUIRED. 106.3.5 MINIMUM PLUMBING PLAN REVIEW CRITERIA | | | FOR BUILDINGS. | | | | | | REVIEW BY LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | (561) 805-6692 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] | | | |
|