| Plan Review Notes For Permit 11040614 |
| Permit Number |
11040614 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-04-27 15:26:35 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. SEE SHEET 11, A .35 FACTOR IS REQUIRED FOR 1 1/2" | | | EDGE DISTANCE. A 3 1/2" EDGE DISTANCE IS REQUIRED TO | | | USE ANCHOR SPACING WHICH IS SPECIFIED IN THE CHARTS, | | | SEE BOX ON SHEET 11 TITLED "EDGE DISTANCE VERSUS | | | SPACING FOR ANCHORS." | | | |
|