| Plan Review Notes For Permit 11040609 |
| Permit Number |
11040609 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-04-26 11:22:15 | PLANS DENIED | | | PROVIDE ACCESS DOORS FOR DUCT DETECTOR. | | | PROVIDE DUCT SIZE ON THE PLANS FOR ALL DUCT. | | | PROVIDE FIRE DAMPERS IN 6X6 DUCT AND 24X18 DUCT'S IN | | | ROOM 101 TOILET. | | | PROVIDE A HANGING DETAIL FOR THE AIR HANDLER ON THE | | | PLANS. | | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 | | | |
|