Plan Review Notes
Plan Review Notes For Permit 11040609
Permit Number 11040609
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2011-04-27 13:39:121411 NORTH FLAGLER DRIVE - LOBBY
 PERMIT #11040609
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 INDENTIFY THE INTERIOR PHARMACY ROOM LOCATED ADJACENT
 TO THE STAIR ENCLOSURE ON SHEET A1.
  
 CEILING NOTES O AND P ARE NOT IDENTIFIED IN THE LEGEND
 ON SHEET A2.
  
 CLEARLY IDENTIFY CEILING HEIGHTS ON SHEET A2. GYPSUM
 BOARD SOFFIT IS INDICATED AS 12'-6" ON SHEET A2,
 HOWEVER, DETAIL 3 OF SHEET A1 INDICATES THE SOFFIT
 ELEVATION IS 8'-1".
  
 MEPF DRAWINGS INDICATE THE 2004 EDITION OF THE FLORIDA
 FIRE PREVENTION CODE. THE 2007 EDITION OF THE FLORIDA
 FIRE PREVENTION CODE IS CURRENTLY IN EFFECT (2006
 EDITION OF NFPA 1 AND NFPA 101).
  
 THE FIRE ALARM SYMBOL (TRIANGLE WITH S) CALLED OUT ON
 SHEET E3 DOES NOT CORRESPOND TO THE LEGEND SHEET.
  
 IDENTIFY THE SPRINKLER HAZARD CLASSIFICATION AND
 SPRINKLER DENSITY ASSOCIATED WITH THE SCOPE OF WORK
 SHOWN ON SHEET F2.
  
 SHEET F2 INDICATES THE USE OF TYCO WINDOW SPRINKLERS;
 HOWEVER, SHEET A1 INDICATES THE GLASS DOORS AND GLASS
 CURTAIN WALLS ARE FIRE RATED. COORDINATE THE INTENDED
 DESIGN. ALSO, STANDARD SPRAY SPRINKLERS ARE LOCATED
 CLOSER THAN SIX FROM ADJACENT WINDOW SPRINKLERS AND MAY
 CAUSE COLD SOLDERING. FOR WINDOW ASSEMBLIES WITH
 VERTICAL MULLIONS, SPRINKLERS ARE REQUIRED TO BE
 LOCATED WITHIN EACH MULLION.
  
 NOTE: IF THE DESIGN INTENT IS TO USE TYCO WINDOW
 SPRINKLERS TO ACHIEVE A FIRE RATED SEPARATION, THE
 SPRINKLERS MUST BE INSTALLED ACCORDING TO THE UL
 LISTING DATA AND SHALL WET THE ENTIRE GLAZING SURFACE.
 SPRINKLERS CANNOT BE USED TO PROTECT OPERABLE DOORS OR
 WINDOWS. THE WINDOW SPRINKLERS DO NOT ALLOW HORIZONTAL
 WINDOW MULLIONS AND REQUIRE THE GLASS CURTAIN WALL TO
 BE ATTACHED TO A THREE FOOT HIGH PONY WALL TO KEEP
 COMBUSTIBLE MATERIALS AT LEAST TWO INCHES AWAY FROM THE
 GLAZING. PAY SPECIAL ATTENTION TO THE GLAZING ASSEMBLY
 AS THE SPRINKLER POSITIONING VARIES FOR BUTT-GLAZED
 INSTALLATIONS COMPARED TO VERTICAL MULLION
 INSTALLATIONS. VERTICAL MULLIONS SHALL BE OF A DEPTH
 THAT PREVENTS COLD SOLDERING OF ADJACENT SPRINKLERS.
 THE SPRINKLER DESIGN SHOULD INDICATE WHICH WINDOW
 SPRINKLER MODEL WILL BE USED (HORIZONTAL SIDEWALL OR
 PENDENT VERTICAL SIDEWALL).
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  