| Plan Review Notes For Permit 11040608 |
| Permit Number |
11040608 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-04-26 12:37:27 | 1258 PALM BEACH LAKES BOULEVARD | | | PERMIT #11040608 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | PROVIDE A PLACARD INDICATING THE USE OF THE TYPE K | | | EXTINGUISHER AS A SECONDARY MEANS TO THE AUTOMATIC FIRE | | | EXTINGUISHING SYSTEM. | | | | | | VERIFY EXHAUST SYSTEM AUTOMATICALLY OPERATES WHENEVER | | | COOKING EQUIPMENT IS TURNED ON. | | | | | | VERFIY DEEP FAT FRYERS ARE LOCATED AT LEAST 16 INCHES | | | AWAY FROM SURFACE FLAMES OF ADJACENT EQUIPMENT OR | | | PROVIDE AN 8 INCH TALL STEEL BAFFLE BETWEEN THE FRYER | | | AND THE STOVE. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW | | | |
|