| 2011-04-26 13:13:51 | 4317 NORTHSHORE DRIVE, SUITE #4211 |
| | PERMIT #11040607 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | DESIGN AND OPERATION OF THE DAY-CARE OCCUPANCY SHALL |
| | COMPLY WITH THE FLORIDA FIRE PREVENTION CODE 2007 |
| | EDITION; SPECIFICALLY CHAPTER 16 TITLED NEW DAY-CARE |
| | OCCUPANCIES. |
| | |
| | DAY-CARE OCCUPANCY SHALL BE SEPARATED FROM ADJACENT |
| | OCCUPANCIES BY AT LEAST A ONE HOUR FIRE RATED BARRIER. |
| | |
| | IDENTIFY THE OCCUPANCY TYPE OF THE TWO ADJACENT TENANT |
| | SPACES. |
| | |
| | EVERY BATHROOM DOOR LOCK SHALL BE DESIGNED TO ALLOW |
| | OPENING OF THE LOCKED DOOR FROM THE OUTSIDE BY AN |
| | OPENING DEVICE THAT SHALL BE READILY ACCESSIBLE TO THE |
| | STAFF. |
| | |
| | TWO EXITS ARE REQUIRED FROM THE BUILDING. CURRENTLY THE |
| | REAR EXIT DISCHARGES INTO THE PROPOSED FENCE ENCLOSURE. |
| | |
| | PROVIDE EMERGENCY LIGHTING. |
| | |
| | INTERIOR WALL AND CEILING FINISH MATERIALS SHALL BE |
| | CLASS A OR CLASS B. |
| | |
| | PROVIDE A MONITORED FIRE ALARM SYSTEM INTEGRATED WITH |
| | SMOKE DETECTORS. SYSTEM SHALL INITIATE BY MANUAL MEANS |
| | AND SMOKE DETECTORS. |
| | |
| | PROVIDE AN EMERGENCY PLAN. |
| | |
| | FIRE DRILLS SHALL BE CONDUCTED MONTHLY AND ALL |
| | OCCUPANTS SHALL PARTICIPATE IN THE DRILL. |
| | |
| | FIRE PREVENTION INSPECTIONS SHALL BE CONDUCTED MONTHLY |
| | BY A TRAINED SENIOR MEMBER OF THE STAFF. A COPY OF THE |
| | LATEST INSPECTION REPORT SHALL BE POSTED IN A |
| | CONSPICUOUS PLACE IN THE DAY-CARE FACILITY. |
| | |
| | STAFF MEMBERS SHALL INSPECT ALL EXIT FACILITIES DAILY |
| | TO ENSURE ALL DOORS AND EXIT PATHS ARE UNLOCKED AND |
| | UNOBSTRUCTED. |
| | |
| | ARTWORK AND TEACHING MATERIALS ATTACHED TO THE WALLS |
| | ARE LIMITED TO 20 PERCENT OF THE WALL AREA OF BUILDINGS |
| | NOT PROTECTED BY AUTOMATIC SPRINKLERS. |
| | |
| | WESLEY JOLIN |
| | WEST PALM BEACH FIRE RESCUE |
| | FIRE & LIFE SAFETY PLAN REVIEW |
| | |