 REVIEW COMMENTS - FIRE DEPARTMENT
  
 DESIGN AND OPERATION OF THE DAY-CARE OCCUPANCY SHALL
 COMPLY WITH THE FLORIDA FIRE PREVENTION CODE 2007
 EDITION; SPECIFICALLY CHAPTER 16 TITLED NEW DAY-CARE
 OCCUPANCIES.
  
 DAY-CARE OCCUPANCY SHALL BE SEPARATED FROM ADJACENT
 OCCUPANCIES BY AT LEAST A ONE HOUR FIRE RATED BARRIER.
  
 IDENTIFY THE OCCUPANCY TYPE OF THE TWO ADJACENT TENANT
 SPACES.
  
 EVERY BATHROOM DOOR LOCK SHALL BE DESIGNED TO ALLOW
 OPENING OF THE LOCKED DOOR FROM THE OUTSIDE BY AN
 OPENING DEVICE THAT SHALL BE READILY ACCESSIBLE TO THE
 STAFF.
  
 TWO EXITS ARE REQUIRED FROM THE BUILDING. CURRENTLY THE
 REAR EXIT DISCHARGES INTO THE PROPOSED FENCE ENCLOSURE.
  
 PROVIDE EMERGENCY LIGHTING.
  
 INTERIOR WALL AND CEILING FINISH MATERIALS SHALL BE
 CLASS A OR CLASS B.
  
 PROVIDE A MONITORED FIRE ALARM SYSTEM INTEGRATED WITH
 SMOKE DETECTORS. SYSTEM SHALL INITIATE BY MANUAL MEANS
 AND SMOKE DETECTORS.
  
 PROVIDE AN EMERGENCY PLAN.
  
 FIRE DRILLS SHALL BE CONDUCTED MONTHLY AND ALL
 OCCUPANTS SHALL PARTICIPATE IN THE DRILL.
  
 FIRE PREVENTION INSPECTIONS SHALL BE CONDUCTED MONTHLY
 BY A TRAINED SENIOR MEMBER OF THE STAFF. A COPY OF THE
 LATEST INSPECTION REPORT SHALL BE POSTED IN A
 CONSPICUOUS PLACE IN THE DAY-CARE FACILITY.
  
 STAFF MEMBERS SHALL INSPECT ALL EXIT FACILITIES DAILY
 TO ENSURE ALL DOORS AND EXIT PATHS ARE UNLOCKED AND
 UNOBSTRUCTED.
  
 ARTWORK AND TEACHING MATERIALS ATTACHED TO THE WALLS
 ARE LIMITED TO 20 PERCENT OF THE WALL AREA OF BUILDINGS
 NOT PROTECTED BY AUTOMATIC SPRINKLERS.
  