| Date |
Text |
| 2011-05-16 16:58:41 | BUILDING PLAN REVIEW |
| | PERMIT: 11040607 |
| | ADD: 4317 NORTHSHORE DR SUITE # 4211 |
| | CONT: TO BE DETERMINED |
| | CONTACT: FANTASIA SIMS |
| | TEL: (561)577-6874 |
| | |
| | 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS* |
| | WEST PALM BEACH AMENDMENTS |
| | 2007 FLORIDA EXISTING BUILDING CODE W/ 2009 FBC |
| | SUPPLEMENTS |
| | |
| | 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | ASBESTOS: IN ACCORDANCE WITH SECTION 553.79 F. S. THIS |
| | IS TO ADVISE YOU OF THE OWNERS OR OPERATOR'S |
| | RESPONSIBILITY TO COMPLY WITH THE STATE & FEDERAL |
| | ASBESTOS REGULATIONS, INCLUDING SECTION 376.60 F. S. |
| | AND CFR 61- NESHAP REQUIREMENTS. REQUIREMENTS INCLUDE- |
| | ASBESTOS SURVEYS AND SUBMISSION OF WRITTEN NOTIFICATION |
| | TO THE DEPARTMENT OF ENVIROMENTAL PROTECTION PRIOR TO: |
| | * DEMOLITION OF ALL REGULATED STRUCTURES; |
| | * MOST RENOVATION ACTIVITIES IN REGULATED STRUCTURES |
| | WHERE ASBESTOS IS DISTURBED OR REMOVED. |
| | NON-COMPLIANCE MAY RESULT IN SEVERE MONETARY PENALTY. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW.THIS REVIEW WILL BE CONDUCTED FOR AN I-2 |
| | OCCUPANCY WITH THE FOLOWING PARAMETERS: |
| | A) CHILD CARE WILL BE PROVIDED ON A 24 HOUR BASIS |
| | B) THE CHILD CARE FACILITY WILL HOUSE MORE THAN 5 |
| | CHILDREN WHO ARE 2 1/2 YEARS OLD AND YOUNGER. |
| | C) IT IS ALSO ASSUMED THAT MEDICAL SUPERVISION IS |
| | PRESENT IN GROUP I-2 FACILITIES. |
| | 2007 FBC-B 308.3.1. |
| | |
| | 1) PLEASE REVIEW THE 2007/ 09 FL EXISTING BLDG CODE |
| | 901.3.1 901.3.1 PARTIAL CHANGE OF OCCUPANCY |
| | CLASSIFICATION. WHERE A PORTION OF AN EXISTING BUILDING |
| | IS CHANGED TO A NEW OCCUPANCY CLASSIFICATION, SECTION |
| | 912 SHALL APPLY. PLEASE PROVIDE THE FOLLOWING |
| | INFORMATION: |
| | 1A) THE MINIMUM BUILDING TYPE OF CONSTRUCTION. FBC-B |
| | TABLE 503 SQ FT AREA / HEIGHT OF BUILDING |
| | |
| | 1B) IF PLEASE PROVIDE IF THE BUILDING IS FIRE |
| | SPRINKLERED PER FBC-B 504.2 OR 903. |
| | |
| | 1C) IF THE DESIGNER OF RECORD HAS DESIGNED THIS TENANT |
| | SPACE PER EXISTING BLDG CODE 912.1.1.1 WITHOUT |
| | SEPERATION OR 912.1.1.2 WITH SEPERATION. |
| | 2007 FBC-B TABLE 508.3.3 & 106.3.5 (4). |
| | |
| | 1D) PLANS INDICATING THE FLOOR PLAN OF THE HAIR SALON |
| | TO SEE WHAT SYSTEMS THAT WILL BE CHANGED. 2007 FBC-B |
| | 106.3.5 & 106.1.2. |
| | |
| | 2) EXISTING BLDG CODE 912.1.2 FIRE PROTECTION AND |
| | INTERIOR FINISH. THE PROVISIONS OF SECTIONS 912.2 AND |
| | 912.3 FOR FIRE PROTECTION AND INTERIOR FINISH, |
| | RESPECTIVELY, SHALL APPLY TO ALL BUILDINGS UNDERGOING A |
| | CHANGE OF OCCUPANCY CLASSIFICATION. |
| | |
| | 2A) EX BLDG CODE 912.2.1 FIRE SPRINKLER SYSTEM. WHERE A |
| | CHANGE IN OCCUPANCY CLASSIFICATION OCCURS THAT REQUIRES |
| | AN AUTOMATIC FIRE SPRINKLER SYSTEM TO BE PROVIDED BASED |
| | ON THE NEW OCCUPANCY IN ACCORDANCE WITH CHAPTER 9 OF |
| | THE FLORIDA BUILDING CODE, BUILDING , SUCH SYSTEM SHALL |
| | BE PROVIDED THROUGHOUT THE AREA WHERE THE CHANGE OF |
| | OCCUPANCY OCCURS. |
| | |
| | 2007 FBC-B F] 903.2.5 GROUP I. AN AUTOMATIC SPRINKLER |
| | SYSTEM SHALL BE PROVIDED THROUGHOUT BUILDINGS WITH A |
| | GROUP I FIRE AREA. |
| | |
| | 2B) EX BLDG CODE 912.2.2 FIRE ALARM AND DETECTION |
| | SYSTEM. WHERE A CHANGE IN OCCUPANCY CLASSIFICATION |
| | OCCURS THAT REQUIRES A FIRE ALARM AND DETECTION SYSTEM |
| | TO BE PROVIDED BASED ON THE NEW OCCUPANCY IN ACCORDANCE |
| | WITH CHAPTER 9 OF THE FLORIDA BUILDING CODE, BUILDING , |
| | SUCH SYSTEM SHALL BE PROVIDED THROUGHOUT THE AREA WHERE |
| | THE CHANGE OF OCCUPANCY OCCURS. EXISTING ALARM |
| | NOTIFICATION APPLIANCES SHALL BE AUTOMATICALLY |
| | ACTIVATED THROUGHOUT THE BUILDING. WHERE THE BUILDING |
| | IS NOT EQUIPPED WITH A FIRE ALARM SYSTEM, ALARM |
| | NOTIFICATION APPLIANCES SHALL BE PROVIDED THROUGHOUT |
| | THE AREA WHERE THE CHANGE OF OCCUPANCY OCCURS AND SHALL |
| | BE AUTOMATICALLY ACTIVATED. |
| | |
| | FBC-B [F] 907.2.6 GROUP I. A MANUAL FIRE ALARM SYSTEM |
| | SHALL BE INSTALLED IN GROUP I OCCUPANCIES. AN |
| | ELECTRICALLY SUPERVISED, AUTOMATIC SMOKE DETECTION |
| | SYSTEM SHALL BE PROVIDED IN ACCORDANCE WITH SECTIONS |
| | 907.2.6.1 AND 907.2.6.2. |
| | |
| | EXCEPTION: MANUAL FIRE ALARM BOXES IN RESIDENT OR |
| | PATIENT SLEEPING AREAS OF GROUP I-1 AND I-2 OCCUPANCIES |
| | SHALL NOT BE REQUIRED AT EXITS IF LOCATED AT ALL |
| | NURSES' CONTROL STATIONS OR OTHER CONSTANTLY ATTENDED |
| | STAFF LOCATIONS, PROVIDED SUCH STATIONS ARE VISIBLE AND |
| | CONTINUOUSLY ACCESSIBLE AND THAT TRAVEL DISTANCES |
| | REQUIRED IN SECTION 907.3.1 ARE NOT EXCEEDED. |
| | |
| | [F] 907.2.6.2 GROUP I-2. CORRIDORS IN NURSING HOMES |
| | (BOTH INTERMEDIATE CARE AND SKILLED NURSING |
| | FACILITIES), DETOXIFICATION FACILITIES AND SPACES |
| | PERMITTED TO BE OPEN TO THE CORRIDORS BY SECTION 407.2 |
| | SHALL BE EQUIPPED WITH AN AUTOMATIC FIRE DETECTION |
| | SYSTEM. HOSPITALS SHALL BE EQUIPPED WITH SMOKE |
| | DETECTION AS REQUIRED IN SECTION 407.2. |
| | |
| | EXCEPTIONS: |
| | |
| | 1. CORRIDOR SMOKE DETECTION IS NOT REQUIRED IN SMOKE |
| | COMPARTMENTS THAT CONTAIN PATIENT SLEEPING UNITS WHERE |
| | PATIENT SLEEPING UNITS ARE PROVIDED WITH SMOKE |
| | DETECTORS THAT COMPLY WITH UL 268. SUCH DETECTORS SHALL |
| | PROVIDE A VISUAL DISPLAY ON THE CORRIDOR SIDE OF EACH |
| | PATIENT SLEEPING UNIT AND AN AUDIBLE AND VISUAL ALARM |
| | AT THE NURSING STATION ATTENDING EACH UNIT. |
| | |
| | 2. CORRIDOR SMOKE DETECTION IS NOT REQUIRED IN SMOKE |
| | COMPARTMENTS THAT CONTAIN PATIENT SLEEPING UNITS WHERE |
| | PATIENT SLEEPING UNIT DOORS ARE EQUIPPED WITH AUTOMATIC |
| | DOOR-CLOSING DEVICES WITH INTEGRAL SMOKE DETECTORS ON |
| | THE UNIT SIDES INSTALLED IN ACCORDANCE WITH THEIR |
| | LISTING, PROVIDED THAT THE INTEGRAL DETECTORS PERFORM |
| | THE REQUIRED ALERTING FUNCTION. |
| | |
| | |
| | 2C) FBC-B 912.3 INTERIOR FINISH. IN AREAS OF THE |
| | BUILDING UNDERGOING THE CHANGE OF OCCUPANCY |
| | CLASSIFICATION, THE INTERIOR FINISH OF WALLS AND |
| | CEILINGS SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING , FOR THE NEW OCCUPANCY |
| | CLASSIFICATION. |
| | |
| | 2C) INTERIOR FINISHES 2007 EX BLDG CODE 912.3 INTERIOR |
| | FINISH. IN AREAS OF THE BUILDING UNDERGOING THE CHANGE |
| | OF OCCUPANCY CLASSIFICATION, THE INTERIOR FINISH OF |
| | WALLS AND CEILINGS SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING , FOR THE NEW |
| | OCCUPANCY CLASSIFICATION. |
| | |
| | 2007 FBC-B 806.1 GENERAL REQUIREMENTS. IN OCCUPANCIES |
| | IN GROUPS A, E, I AND R-1 AND DORMITORIES IN GROUP R-2, |
| | CURTAINS, DRAPERIES, HANGINGS AND OTHER DECORATIVE |
| | MATERIALS SUSPENDED FROM WALLS OR CEILINGS SHALL MEET |
| | THE FLAME PROPAGATION PERFORMANCE CRITERIA OF NFPA 701 |
| | IN ACCORDANCE WITH SECTION 806.2 OR BE NONCOMBUSTIBLE. |
| | |
| | IN GROUPS I-1 AND I-2, COMBUSTIBLE DECORATIVE MATERIALS |
| | SHALL MEET THE FLAME PROPAGATION CRITERIA OF NFPA 701 |
| | UNLESS THE DECORATIVE MATERIALS, INCLUDING, BUT NOT |
| | LIMITED TO, PHOTOGRAPHS AND PAINTINGS, ARE OF SUCH |
| | LIMITED QUANTITIES THAT A HAZARD OF FIRE DEVELOPMENT OR |
| | SPREAD IS NOT PRESENT. IN GROUP I-3, COMBUSTIBLE |
| | DECORATIVE MATERIALS ARE PROHIBITED. |
| | |
| | FIXED OR MOVABLE WALLS AND PARTITIONS, PANELING, WALL |
| | PADS AND CRASH PADS APPLIED STRUCTURALLY OR FOR |
| | DECORATION, ACOUSTICAL CORRECTION, SURFACE INSULATION |
| | OR OTHER PURPOSES SHALL BE CONSIDERED INTERIOR FINISH |
| | IF THEY COVER 10 PERCENT OR MORE OF THE WALL OR OF THE |
| | CEILING AREA, AND SHALL NOT BE CONSIDERED DECORATIVE |
| | MATERIALS OR FURNISHINGS. |
| | |
| | 3) 2007 EX BLDG CODE 912.1.4 ACCESSIBILITY. ALL |
| | BUILDINGS UNDERGOING A CHANGE OF OCCUPANCY |
| | CLASSIFICATION SHALL COMPLY WITH SECTION 912.8. |
| | 912.8 ACCESSIBILITY. EXISTING BUILDINGS OR PORTIONS |
| | THEREOF THAT UNDERGO A CHANGE OF GROUP OR OCCUPANCY |
| | CLASSIFICATION SHALL COMPLY WITH CHAPTER 11 OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | 2007/09 FBC-B 11-4.1.62) ALTERATIONS TO AN AREA |
| | CONTAINING A PRIMARY FUNCTION. IN ADDITION TO THE |
| | REQUIREMENTS OF SECTION 11-4.1.6(1), AN ALTERATION THAT |
| | AFFECTS OR COULD AFFECT THE USABILITY OF OR ACCESS TO |
| | AN AREA CONTAINING A PRIMARY FUNCTION SHALL BE MADE SO |
| | AS TO ENSURE THAT, TO THE MAXIMUM EXTENT FEASIBLE, THE |
| | PATH OF TRAVEL TO THE ALTERED AREA AND THE RESTROOMS, |
| | TELEPHONES, AND DRINKING FOUNTAINS SERVING THE ALTERED |
| | AREA, ARE READILY ACCESSIBLE TO AND USABLE BY |
| | INDIVIDUALS WITH DISABILITIES, UNLESS SUCH ALTERATIONS |
| | ARE DISPROPORTIONATE TO THE OVERALL ALTERATIONS TIN |
| | TERMS OF COST AND SCOPE. |
| | ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF |
| | TRAVEL TO ALTERED AREAS SHALL BE DEEMED |
| | DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE |
| | COST EXCEEDS 20 PERCENT OF THE COST OF THE ALTERATION |
| | TO THE PRIMARY FUNCTION AREA. |
| | |
| | DUTY TO PROVIDE ACCESSIBLE FEATURES IN THE EVENT OF |
| | DISPROPORTIONALITY. |
| | |
| | (1) WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE |
| | PATH OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS |
| | DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION, |
| | THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE |
| | EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING |
| | DISPROPORTIONATE COSTS. |
| | |
| | (2)(A) IN CHOOSING WHICH ACCESSIBLE ELEMENTS TO |
| | PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE ELEMENTS |
| | THAT WILL PROVIDE THE GREATEST ACCESS, IN THE FOLLOWING |
| | ORDER: |
| | |
| | (I) AN ACCESSIBLE ENTRANCE; |
| | |
| | (II) AN ACCESSIBLE ROUTE TO THE ALTERED AREA: |
| | |
| | (III) AT LEAST ONE ACCESSIBLE RESTROOM FOR EACH SEX OR |
| | A SINGLE UNISEX RESTROOM: |
| | |
| | (IV) ACCESSIBLE TELEPHONES; |
| | |
| | (V) ACCESSIBLE DRINKING FOUNTAINS; AND |
| | |
| | (VI) WHEN POSSIBLE, ADDITIONAL ACCESSIBLE ELEMENTS SUCH |
| | AS PARKING, STORAGE, AND ALARMS. |
| | |
| | |
| | |
| | 4) 2007 EX BLDG CODE 912.4 MEANS OF EGRESS, GENERAL. |
| | HAZARD CATEGORIES IN REGARD TO LIFE SAFETY AND MEANS OF |
| | EGRESS SHALL BE IN ACCORDANCE WITH TABLE 912.4. |
| | I-2 INSTITUTIONAL 2 |
| | HAIR SALON: BUSINESS 4 |
| | |
| | 912.4.1 MEANS OF EGRESS FOR CHANGE TO HIGHER HAZARD |
| | CATEGORY. WHEN A CHANGE OF OCCUPANCY GROUP IS MADE TO A |
| | HIGHER HAZARD CATEGORY (LOWER NUMBER) AS SHOWN IN TABLE |
| | 912.4, THE MEANS OF EGRESS SHALL COMPLY WITH THE |
| | REQUIREMENTS OF CHAPTER 10 OF THE FLORIDA BUILDING |
| | CODE, BUILDING . |
| | |
| | 2007 FBC-B PLEASE PROVIDE THE OCCUPANT LOAD ACCORDING |
| | TO 2007 TABLE 1004.1.1 FBC-B FOR I-2 OCCUPANCY, IF |
| | DAYCARE OCCUPANCY THIS WILL BE FORE LESS THAN 24 HR |
| | STAY THE PLANS AND PERMIT APPLICATION WILL NEED TO |
| | REFLECT THIS CHANGE OF OCCUPANCY. |
| | |
| | IF THIS IS A I-2 OCCUPANCY WHERE THE OCCUPANTS WILL BE |
| | HERE MORE THAN 24 HRS, THIS IS DIFFERENT FROM BEING |
| | OPEN 24 HOURS, PLEASE REVIEW THE REQUIREMENTS FOR |
| | PATIENT SLEEPING ROOMS AND SMOKE BARRIERS AND REFUGE |
| | AREAS. |
| | |
| | PLEASE SEE REQUIREMENTS FOR I-2 OCCUPANCY EXIST BLDG |
| | CODE 705.4.1.2. |
| | |
| | JAMES A. WITMER C.B.O. |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: (561)805-6715 |
| | FAX:(561)805-6731 |
| | E-MAIL: [email protected] |
| | |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |