| Plan Review Notes For Permit 11040584 |
| Permit Number |
11040584 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-04-22 09:11:10 | PROVIDE A ONE LINE DIAGRAM SHOWING THE EXISTING | | | SERVICE, MAIN DISCONNECTS, VOLTAGE, SERVICE GROUNDING | | | AND FEEDERS. NEC 215.5, 215.6. | | | PROVIDE SPECIFICATION ON THE NEW DISCONNECT SHOWING THE | | | EQUIPMENT IS SUFFICIENT TO INTERRUPT THE AVAILABLE | | | FAULT CURRENT. NEC 110.9 | | | PROVIDE A FAULT CURRENT CALCULATION TO SUPPORT THE | | | EQUIPMENT SELECTION. NEC 110.10 | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|