Plan Review Notes
Plan Review Notes For Permit 11040561
Permit Number 11040561
Review Stop E
Sequence Number 1
Notes
Date Text
2011-04-22 09:55:22TO LM
2011-04-22 09:54:55 
 PROVIDE A WIRING DIAGRAM AND MOUNTING DETAIL FOR THE
 TWO FANS.
 FANS AND WIRING MUST BE RATED FOR DAMP LOCATIONS.
 PROVIDE ENGINEERING INDICATING THE EXISTING CANOPY CAN
 SUPPORT THE WEIGHT OF THE NEW EQUIPMENT.
 PROVIDE A DIMENSIONED PLAN WHICH SHOWS HEIGHT OF FAN
 BLADES ABOVE THE SIDEWALK.
 PROVIDE ZONING APPROVAL FOR THE LOCATION OF THE FANS.
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  
  
  
  