| Plan Review Notes For Permit 11040544 |
| Permit Number |
11040544 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2011-05-04 12:01:55 | PREVIOUS ELECTRIC REVIEW COMMENTS WERE NOT ADDRESSED. | | | | | | REQUIRES A SEPARATE ELECTRIC PERMIT AND PLAN. | | | SHOW EXISTING SERVICE LOCATION WITH SAFETY CLEARANCES, | | | POWER PLAN AND RISER. | | | SHOW EXIT SIGNS AND EMERGENCY LIGHTING. | | | SHOW GFCI PROTECTION ON APPROPRIATE OUTLETS. | | | | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | | | | | | | | | | |
|