| Plan Review Notes For Permit 11040532 |
| Permit Number |
11040532 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-04-25 09:11:07 | | | | ELECTRICAL PLAN INSUFFICIENTLY DETAILED TO APPROVE. | | | PLEASE PROVIDE THE FOLLOWING. | | | | | | SHOW SIZE OF THE NEW ELECTRICAL PANEL. PROVIDE A PANEL | | | SCHEDULE SHOWING NEW AND EXISTING LOADS. NEC 215.5 | | | PROVIDE GFCI PROTECTED OUTLETS IN THE BATHROOMS. NEC | | | 210.52 | | | ALL GENERAL PURPOSE OUTLETS INCLUDING THOSE IN THE | | | BEDROOMS AND SMOKE ALARMS MUST BE AFCI PROTECTED. NEC | | | 210.12 | | | SHOW KITCHEN CIRCUITS WITH GFCI PROTECTION. COUNTER TOP | | | RIGHT OF STOVE REQUIRES A RECEPTACLE. NEC 210.8, 210.52 | | | INTERCONNECT THE SD?S. FBC R313 | | | NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11 | | | A GFCI PROTECTED RECEPTACLE IS REQUIRED ON THE BALCONY. | | | NEC 210.52 | | | | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|