Plan Review Notes
Plan Review Notes For Permit 11040525
Permit Number 11040525
Review Stop B
Sequence Number 1
Notes
Date Text
2011-04-22 08:14:072007 FBC WITH 2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) SUBMIT TWO COPIES OF ENERGY CALCULATIONS FOR THE
 ADDITION. NOTE: IF FORM 1100B-08 IS USED R-13
 INSULATION IS REQUIRED IN THE EXTERIOR FRAME WALLS.
  
 2) PRODUCT APPROVALS WERE SUBMITTED FOR A FIXED IMPACT
 RATED WINDOW. THIS TYPE WINDOW WAS NOT INDICATED ON THE
 PLANS. PLEASE CLARIFY.
  
 3) THE PRODUCT APPROVALS FOR THE DOUBLE HUNG AND FIXED
 IMPACT RATED WINDOWS SPECIFY DESIGN PRESSURES OF +55
 AND -65 PSF. THE PLANS SPECIFY THE COMPONENT AND
 CLADDING PRESSURES AS +49.42, -66.08 PSF IN WALL ZONE
 5. THEREFORE, THE NEGATIVE PRESSURES OF THE PRODUCTS
 ARE TOO LOW FOR USE IN WALL ZONE 5.
  
 4) SPECIFY THE APPROVED ASSEMBLY, FASTENING OPTION AND
 DESIGN PRESSURE FROM THE GAF ROOFING PRODUCT APPROVAL
 THAT WILL BE USED. SUBMIT TWO SETS OF SIGNED AND SEALED
 RAS CALCULATIONS FOR THE ENHANCED FASTENING OF THE BASE
 SHEET AS REQUIRED BY LIMITATION NUMBER 7 ON PAGE 19 OF
 THE PRODUCT APPROVAL.
  
 5) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR
 THE PROJECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]