2011-08-19 13:06:20BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- ENERGY CALCULATIONS SUBMITTED: A) SHOW PTAC UNIT FOR
 HEATING AND COOLING. PLANS SUBMITTED SHOW SPLIT A/C
 UNIT. REVISE PLANS AS REQUIRED. PTAC UNIT FOR HEATING
 MUST BE HARD WIRED AND A/C PERMIT IS REQUIRED (PROVIDE
 COMPLETE INFORMATION FOR A/C UNDER A SEPARATE PERMIT) .
 SEE SEC R303.8.
 B) REVISE MATERIAL OF DOOR TO BE USED. IT ISN'T WOOD.
 SEE NOA SUBMITTED.
 C) PROVIDE CORRECT BUILDER'S NAME.
  
 2- ENTRY DOOR NOA SUBMITTED IS FOR A NON-IMPACT
 DOOR/SIDELITE. PROVIDE COMPLETE SHUTTERS INFORMATION.
 PROVIDE PRODUCT APPROVAL AND COMPLETE INSTALLATION
 SCHEDULE.
 ARCHITECT TO REVIEW PRODUCT APPROVAL PRIOR TO
 SUBMITTAL. SEC. 106.3.3 CITY AMENDMENTS.
  