| 2011-07-21 09:50:39 | RESIDENTIAL (R3) ALTERATION BUILDING REVIEW SECOND |
| | CHECKLIST. |
| | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. 2007 |
| | FBC-EXISTING BUILDING. |
| | |
| | 1- A) ACCORDING TO 2009 REVISIONS SEC. R301.2.1.4.3 |
| | THIS BUILDING IS LOCATED ON EXPOSURE "C" NOT "B". |
| | ARCHITECT TO REVISE THE BUILDING EXPOSURE ON PROJECT |
| | INFORMATION TABLE ON SHEET A-1. |
| | (REPEAT COMMENT. NOT ADDRESSED). |
| | |
| | B) REVISE THE DOORS/WINDOWS DESIGN PRESSURES ON SHEET |
| | A-1 AND A-2 TO CORRESPOND TO EXPOSURE "C". SEE ITEM |
| | 1(A) ABOVE. (REPEAT COMMENT. NOT ADDRESSED). |
| | |
| | 2- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| | N1100.3 OF 2007 FLORIDA RESIDENTIAL CODE CHAPTER 11. |
| | (REPEAT COMMENT. NOT ADDRESSED). |
| | |
| | 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9B-72 FOR: |
| | A) ROOF SHINGLES AS SHOWN ON PLANS. (REPEAT COMMENT. |
| | NOT ADDRESSED). |
| | |
| | B) FLAT ROOF AS SHOWN ON PLANS. AND, MARK /IDENTIFY |
| | WHICH APPROVED ROOFING ASSEMBLY IS GOING TO BE |
| | INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN |
| | PRESSURES OF SEC. R301. |
| | PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT |
| | PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL |
| | LIMITATION #7. IF GENERAL LIMITATION #7 REQUIRES SIGNED |
| | AND SEALED CALCULATIONS, THEN PROVIDE THEM SIGNED AND |
| | SEALED. (REPEAT COMMENT. CERTAINTEED INFORMATION |
| | SUBMITTED IS NOT A PRODUCT APPROVAL. CERTAINTEED |
| | PRODUCT REQUIRES SIGNED AND SEALED RAS 117 |
| | CALCULATIONS. PRODUCT APPROVAL LIMITATIONS). |
| | |
| | C) EXTERIOR DOORS AS SHOWN ON PLANS. ENTRY DOOR WITH |
| | SIDELITE ASSEMBLY AT GUEST HOUSE AND DOOR AT STORAGE |
| | ENTRY. (REPEAT COMMENT. GUEST HOUSE NOA 08-0312.09 |
| | SUBMITTED EXPIRED ON MAY 25, 2011. NEED CURRENT NOA. |
| | AND, PRODUCT APPROVAL FOR STORAGE ROOM WAS NOT |
| | SUBMITTED). |
| | |
| | D) WINDOW MULLIONS AS SHOWN ON PLANS. (REPEAT COMMENT. |
| | NOT ADDRESSED). |
| | |
| | E) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON |
| | PLANS/SECTIONS AND DETAILS. PROVIDE ONLY THE PRODUCT |
| | APPROVAL COVER AND PAGE SHOWING THE SPECIFIED |
| | CONNECTOR. THIS APPLIES TO STRUCTURAL CONNECTORS ONLY. |
| | ALL OTHER PRODUCT APPROVALS REQUIRE FULL REPORT. |
| | (REPEAT COMMENT. NOT ADDRESSED). |
| | |
| | F) HARDI-PLAN SIDING AS SPECIFIED ON SHEET A-3 TYPICAL |
| | BEARING WALL DETAIL AND EXTERIOR ELEVATIONS. NOTE: |
| | HISTORIC NEEDS TO APPROVE IT ALSO. WOOD SIDING DOESN'T |
| | REQUIRE PRODUCT APPROVAL, BUT STILL NEED TO COORDINATE |
| | WITH HISTORIC APPROVAL. (REPEAT COMMENT. NOT |
| | ADDRESSED). |
| | |
| | G) HURRICANE SHUTTERS IF DOORS AND WINDOWS PROVIDED |
| | DON'T HAVE IMPACT GLASS. CLEARLY IDENTIFY ON PRODUCT |
| | APPROVAL SPECIFIC SHUTTERS MOUNTING CONDITIONS AND |
| | PROVIDE COMPLETE INSTALLATION SCHEDULE. |
| | |
| | H) SIDELITE WINDOW AT GUEST HOUSE ENTRY DOOR. |
| | COORDINATE WITH ITEM #3(D) ABOVE. (REPEAT COMMENT. NOT |
| | ADDRESSED). |
| | |
| | 4- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC. |
| | (REPEAT COMMENT. NOT ADDRESSED). |
| | |
| | 5- ARCHITECT TO SIGN AND SEAL BOTH SETS OF PLANS. ONLY |
| | ONE WAS SIGNED AND SEALED. CHAPTER 481 FLORIDA STATUTE. |
| | (REPEAT COMMENT. NOT ADDRESSED). |
| | |
| | 6- ARCHITECT TO PROVIDE IN THE TITLE BLOCK ALL THE |
| | INFORMATION REQUIRED BY SEC. 61G1-16004 OF THE FLORIDA |
| | ADMINISTRATIVE CODE AND CHAPTER 481 FLORIDA STATUTE. |
| | MISSING THE ARCHITECT'S AND FIRM LICENSE NUMBER AND |
| | DATE WHEN DRAWINGS WHERE PREPARED. (REPEAT COMMENT. NOT |
| | ADDRESSED). |
| | |
| | 7- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 |
| | FLORIDA STATUTE. |
| | ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK |
| | UP. |
| | |
| | 8- REVISE ROOF SHEATHING NAILING SPECIFICATIONS. ROOF |
| | ZONE #3 REQUIRES 8D RING SHANK NAILS AT 4"O.C. ALSO. |
| | REVISE ROOF NAILING PATTERN ON SHEET A-1 PROJECT |
| | INFORMATION TABLE, ON SHEET A-2 SECTION AND ON SHEET |
| | A-3 TYPICAL BEARING WALL DETAIL. SEC. R803.2.3.1. |
| | (REPEAT COMMENT. NOT ADDRESSED). |
| | |
| | 9 - PROJECT INFORMATION TABLE ON SHEET A-1: A) REVISE |
| | OCCUPANCY CLASS. THIS IS NOT R1. THIS IS R3. (REPEAT |
| | COMMENT. NOT ADDRESSED). |
| | |
| | B) SPECIFY TYPE OF CONSTRUCTION. INFORMATION SUBMITTED |
| | IS NOT CORRECT. (REPEAT COMMENT. NOT ADDRESSED). |
| | |
| | C) SPECIFY TYPE OF ALTERATION AS REQUIRED BY SEC. 401.4 |
| | OF 2007 FBC-EXISTING. (REPEAT COMMENT. NOT ADDRESSED). |
| | |
| | 10- SHEET A-2: A) ROOF PROFILE SHOWN ON FRONT |
| | ELEVATION, REAR ELEVATION AND LEFT ELEVATION DOESN'T |
| | MATCH ROOF FRAMING PLAN LAYOUT SHOWN ON SHEET A-1. |
| | REVISE AS REQUIRED. (REPEAT COMMENT. NOT ADDRESSED). |
| | |
| | B) REAR ELEVATION IS MISSING THE WINDOW ON THE STORAGE |
| | ROOM AS SHOWN ON FLOOR PLAN ON SHEET A-1. REVISE AS |
| | REQUIRED. (REPEAT COMMENT. NOT ADDRESSED). |
| | |
| | 11- BRING ALL REVISED PLANS AND PRODUCT APPROVALS FOR |
| | HISTORIC APPROVAL PRIOR TO SUBMITTING TO THIS OFFICE TO |
| | AVOID CONFLICTS OR DELAYS. |
| | |