Plan Review Notes
Plan Review Notes For Permit 11040492
Permit Number 11040492
Review Stop B
Sequence Number 2
Notes
Date Text
2011-07-21 09:50:39RESIDENTIAL (R3) ALTERATION BUILDING REVIEW SECOND
 CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. 2007
 FBC-EXISTING BUILDING.
  
 1- A) ACCORDING TO 2009 REVISIONS SEC. R301.2.1.4.3
 THIS BUILDING IS LOCATED ON EXPOSURE "C" NOT "B".
 ARCHITECT TO REVISE THE BUILDING EXPOSURE ON PROJECT
 INFORMATION TABLE ON SHEET A-1.
 (REPEAT COMMENT. NOT ADDRESSED).
  
 B) REVISE THE DOORS/WINDOWS DESIGN PRESSURES ON SHEET
 A-1 AND A-2 TO CORRESPOND TO EXPOSURE "C". SEE ITEM
 1(A) ABOVE. (REPEAT COMMENT. NOT ADDRESSED).
  
 2- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 N1100.3 OF 2007 FLORIDA RESIDENTIAL CODE CHAPTER 11.
 (REPEAT COMMENT. NOT ADDRESSED).
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) ROOF SHINGLES AS SHOWN ON PLANS. (REPEAT COMMENT.
 NOT ADDRESSED).
  
 B) FLAT ROOF AS SHOWN ON PLANS. AND, MARK /IDENTIFY
 WHICH APPROVED ROOFING ASSEMBLY IS GOING TO BE
 INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301.
 PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT
 PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL
 LIMITATION #7. IF GENERAL LIMITATION #7 REQUIRES SIGNED
 AND SEALED CALCULATIONS, THEN PROVIDE THEM SIGNED AND
 SEALED. (REPEAT COMMENT. CERTAINTEED INFORMATION
 SUBMITTED IS NOT A PRODUCT APPROVAL. CERTAINTEED
 PRODUCT REQUIRES SIGNED AND SEALED RAS 117
 CALCULATIONS. PRODUCT APPROVAL LIMITATIONS).
  
 C) EXTERIOR DOORS AS SHOWN ON PLANS. ENTRY DOOR WITH
 SIDELITE ASSEMBLY AT GUEST HOUSE AND DOOR AT STORAGE
 ENTRY. (REPEAT COMMENT. GUEST HOUSE NOA 08-0312.09
 SUBMITTED EXPIRED ON MAY 25, 2011. NEED CURRENT NOA.
 AND, PRODUCT APPROVAL FOR STORAGE ROOM WAS NOT
 SUBMITTED).
  
 D) WINDOW MULLIONS AS SHOWN ON PLANS. (REPEAT COMMENT.
 NOT ADDRESSED).
  
 E) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS/SECTIONS AND DETAILS. PROVIDE ONLY THE PRODUCT
 APPROVAL COVER AND PAGE SHOWING THE SPECIFIED
 CONNECTOR. THIS APPLIES TO STRUCTURAL CONNECTORS ONLY.
 ALL OTHER PRODUCT APPROVALS REQUIRE FULL REPORT.
 (REPEAT COMMENT. NOT ADDRESSED).
  
 F) HARDI-PLAN SIDING AS SPECIFIED ON SHEET A-3 TYPICAL
 BEARING WALL DETAIL AND EXTERIOR ELEVATIONS. NOTE:
 HISTORIC NEEDS TO APPROVE IT ALSO. WOOD SIDING DOESN'T
 REQUIRE PRODUCT APPROVAL, BUT STILL NEED TO COORDINATE
 WITH HISTORIC APPROVAL. (REPEAT COMMENT. NOT
 ADDRESSED).
  
 G) HURRICANE SHUTTERS IF DOORS AND WINDOWS PROVIDED
 DON'T HAVE IMPACT GLASS. CLEARLY IDENTIFY ON PRODUCT
 APPROVAL SPECIFIC SHUTTERS MOUNTING CONDITIONS AND
 PROVIDE COMPLETE INSTALLATION SCHEDULE.
  
 H) SIDELITE WINDOW AT GUEST HOUSE ENTRY DOOR.
 COORDINATE WITH ITEM #3(D) ABOVE. (REPEAT COMMENT. NOT
 ADDRESSED).
  
 4- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC.
 (REPEAT COMMENT. NOT ADDRESSED).
  
 5- ARCHITECT TO SIGN AND SEAL BOTH SETS OF PLANS. ONLY
 ONE WAS SIGNED AND SEALED. CHAPTER 481 FLORIDA STATUTE.
 (REPEAT COMMENT. NOT ADDRESSED).
  
 6- ARCHITECT TO PROVIDE IN THE TITLE BLOCK ALL THE
 INFORMATION REQUIRED BY SEC. 61G1-16004 OF THE FLORIDA
 ADMINISTRATIVE CODE AND CHAPTER 481 FLORIDA STATUTE.
 MISSING THE ARCHITECT'S AND FIRM LICENSE NUMBER AND
 DATE WHEN DRAWINGS WHERE PREPARED. (REPEAT COMMENT. NOT
 ADDRESSED).
  
 7- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
 ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK
 UP.
  
 8- REVISE ROOF SHEATHING NAILING SPECIFICATIONS. ROOF
 ZONE #3 REQUIRES 8D RING SHANK NAILS AT 4"O.C. ALSO.
 REVISE ROOF NAILING PATTERN ON SHEET A-1 PROJECT
 INFORMATION TABLE, ON SHEET A-2 SECTION AND ON SHEET
 A-3 TYPICAL BEARING WALL DETAIL. SEC. R803.2.3.1.
 (REPEAT COMMENT. NOT ADDRESSED).
  
 9 - PROJECT INFORMATION TABLE ON SHEET A-1: A) REVISE
 OCCUPANCY CLASS. THIS IS NOT R1. THIS IS R3. (REPEAT
 COMMENT. NOT ADDRESSED).
  
 B) SPECIFY TYPE OF CONSTRUCTION. INFORMATION SUBMITTED
 IS NOT CORRECT. (REPEAT COMMENT. NOT ADDRESSED).
  
 C) SPECIFY TYPE OF ALTERATION AS REQUIRED BY SEC. 401.4
 OF 2007 FBC-EXISTING. (REPEAT COMMENT. NOT ADDRESSED).
  
 10- SHEET A-2: A) ROOF PROFILE SHOWN ON FRONT
 ELEVATION, REAR ELEVATION AND LEFT ELEVATION DOESN'T
 MATCH ROOF FRAMING PLAN LAYOUT SHOWN ON SHEET A-1.
 REVISE AS REQUIRED. (REPEAT COMMENT. NOT ADDRESSED).
  
 B) REAR ELEVATION IS MISSING THE WINDOW ON THE STORAGE
 ROOM AS SHOWN ON FLOOR PLAN ON SHEET A-1. REVISE AS
 REQUIRED. (REPEAT COMMENT. NOT ADDRESSED).
  
 11- BRING ALL REVISED PLANS AND PRODUCT APPROVALS FOR
 HISTORIC APPROVAL PRIOR TO SUBMITTING TO THIS OFFICE TO
 AVOID CONFLICTS OR DELAYS.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712