Plan Review Notes
Plan Review Notes For Permit 11040492
Permit Number 11040492
Review Stop B
Sequence Number 1
Notes
Date Text
2011-05-19 13:30:09RESIDENTIAL (R3) ALTERATION BUILDING REVIEW CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. 2007
 FBC-EXISTING.
  
 1- A) ACCORDING TO 2009 REVISIONS SEC. R301.2.1.4.3
 THIS BUILDING IS LOCATED ON EXPOSURE "C" NOT "B".
 ARCHITECT TO REVISE THE BUILDING EXPOSURE ON PROJECT
 INFORMATION TABLE ON SHEET A-1.
  
 B) REVISE THE DOORS/WINDOWS DESIGN PRESSURES ON SHEET
 A-1 AND A-2 TO CORRESPOND TO EXPOSURE "C". SEE ITEM
 1(A) ABOVE.
  
 2- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 N1100.3 OF 2007 FLORIDA RESIDENTIAL CODE CHAPTER 11.
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) ROOF SHINGLES AS SHOWN ON PLANS.
  
 B) FLAT ROOF AS SHOWN ON PLANS. AND, MARK /IDENTIFY
 WHICH APPROVED ROOFING ASSEMBLY IS GOING TO BE
 INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301.
 PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT
 PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL
 LIMITATION #7. IF GENERAL LIMITATION #7 REQUIRES SIGNED
 AND SEALED CALCULATIONS, THEN PROVIDE THEM SIGNED AND
 SEALED.
  
 C) EXTERIOR DOORS AS SHOWN ON PLANS. ENTRY DOOR WITH
 SIDELITE ASSEMBLY AT GUEST HOUSE AND DOOR AT STORAGE
 ENTRY.
  
 D) WINDOWS AS SHOWN ON PLANS.
  
 E) WINDOW MULLIONS AS SHOWN ON PLANS. COORDINATE WITH
 ITEMS #3(C) AND #3(I).
  
 F) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS/SECTIONS AND DETAILS. PROVIDE ONLY THE PRODUCT
 APPROVAL COVER AND PAGE SHOWING THE SPECIFIED
 CONNECTOR. THIS APPLIES TO STRUCTURAL CONNECTORS ONLY.
 ALL OTHER PRODUCT APPROVALS REQUIRE FULL REPORT.
  
 G) HARDI-PLAN SIDING AS SPECIFIED ON SHEET A-3 TYPICAL
 BEARING WALL DETAIL. NOTE: HISTORIC NEEDS TO APPROVE IT
 ALSO. WOOD SIDING DOESN'T REQUIRE PRODUCT APPROVAL, BUT
 STILL NEED TO COORDINATE WITH HISTORIC APPROVAL.
  
 H) HURRICANE SHUTTERS IF DOORS AND WINDOWS PROVIDED
 DON'T HAVE IMPACT GLASS. CLEARLY IDENTIFY ON PRODUCT
 APPROVAL SPECIFIC SHUTTERS MOUNTING CONDITIONS AND
 PROVIDE COMPLETE INSTALLATION SCHEDULE.
  
 I) SIDELITE WINDOW AT GUEST HOUSE ENTRY DOOR.
 COORDINATE WITH ITEM #3(C) ABOVE.
  
 4- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC.
  
 5- ARCHITECT TO SIGN AND SEAL BOTH SETS OF PLANS. ONLY
 ONE WAS SIGNED AND SEALED. CHAPTER 481 FLORIDA STATUTE.
  
 6- ARCHITECT TO PROVIDE IN THE TITLE BLOCK ALL THE
 INFORMATION REQUIRED BY SEC. 61G1-16004 OF THE FLORIDA
 ADMINISTRATIVE CODE AND CHAPTER 481 FLORIDA STATUTE.
 MISSING THE ARCHITECT'S AND FIRM LICENSE NUMBER AND
 DATE WHEN DRAWINGS WHERE PREPARED.
  
 7- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
 ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK
 UP.
  
 8- REVISE ROOF SHEATHING NAILING SPECIFICATIONS. ROOF
 ZONE #3 REQUIRES 8D RING SHANK NAILS AT 4"O.C. ALSO.
 REVISE ROOF NAILING PATTERN ON SHEET A-1 PROJECT
 INFORMATION TABLE, ON SHEET A-2 SECTION AND ON SHEET
 A-3 TYPICAL BEARING WALL DETAIL. SEC. R803.2.3.1.
  
 9- PROJECT INFORMATION TABLE ON SHEET A-1: A) REVISE
 OCCUPANCY CLASS. THIS IS NOT R1. THIS IS R3.
  
 B) SPECIFY TYPE OF CONSTRUCTION. INFORMATION SUBMITTED
 IS NOT CORRECT.
  
 C) SPECIFY TYPE OF ALTERATION AS REQUIRED BY SEC. 401.4
 OF 2007 FBC-EXISTING.
  
 10- SHEET A-2: A) ROOF PROFILE SHOWN ON FRONT
 ELEVATION, REAR ELEVATION AND LEFT ELEVATION DOESN'T
 MATCH ROOF FRAMING PLAN LAYOUT SHOWN ON SHEET A-1.
 REVISE AS REQUIRED.
  
 B) REAR ELEVATION IS MISSING THE WINDOW ON THE STORAGE
 ROOM AS SHOWN ON FLOOR PLAN ON SHEET A-1. REVISE AS
 REQUIRED.
  
 11- BRING ALL REVISED PLANS AND PRODUCT APPROVALS FOR
 HISTORIC APPROVAL PRIOR TO SUBMITTING TO THIS OFFICE TO
 AVOID CONFLICTS OR DELAYS.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712