| 2011-04-20 11:11:20 | PROVIDE A LOAD CALCULATION FOR THE UNDERSIZED NEUTRALS | | | (GROUNDED CONDUCTORS) OR PROVIDE FULL SIZED NEUTRALS. | | | NEC 215.2, 220.61, 230.42 | | | PROVIDE AN EQUIPMENT GROUNDING CONDUCTOR. NEC 250.110, | | | 250.118 | | | PROVIDE A ONE LINE DIAGRAM SHOWING THE EXISTING | | | SERVICE, VOLTAGE, SERVICE GROUNDING AND FEEDERS. NEC | | | 215.5, 215.6. | | | | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|