| 2011-05-18 15:59:10 | RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW |
| | CHECKLIST. |
| | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. 2007 |
| | FBC-EXISTING. |
| | |
| | 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9B-72 FOR: |
| | |
| | A) WINDOWS AS SPECIFIED ON PLANS. |
| | |
| | B) HURRICANE SHUTTERS IF WINDOWS AND DOORS TO BE |
| | INSTALLED DON'T HAVE IMPACT GLASS. AND, CLEARLY MARK ON |
| | PRODUCT APPROVAL DRAWINGS SPECIFIC SHUTTERS MOUNTING |
| | CONDITIONS AND SPECIFIC ANCHOR TYPE AND SPACING TO BE |
| | USED. ALSO, PROVIDE A COMPLETE INSTALLATION SCHEDULE AS |
| | REQUIRED BY THE CITY IMPLEMENTATION STANDARD FOR |
| | WIND-BORNE DEBRIS IMPACT PROTECTION. |
| | |
| | C) EXTERIOR DOORS AS SHOWN ON PLANS. |
| | |
| | D) WINDOW MULLIONS AS SHOWN ON PLANS. |
| | |
| | 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC. |
| | |
| | 3- SHEET A-1: |
| | A) SPECIFY SAFETY GLASS ON WINDOW ADJACENT TO THE DOOR |
| | IN THE FAMILY ROOM AREA AND WINDOW BY THE BATH TUB |
| | AREA. SEC. R308.4. |
| | |
| | B) ENGINEER TO CLARIFY WHY THE DESIGN PRESSURES FOR THE |
| | EXTERIOR DOORS ARE SO LOW. PROVIDE CALCULATIONS TO |
| | VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. |
| | R301. |
| | |
| | C) ENGINEER TO SPECIFY THE BUILDING CONSTRUCTION TYPE |
| | ON THE CODE INFORMATION TABLE. THIS ITEM WAS LEFT BLANK |
| | ON DRAWING SUBMITTED. SEC. 106.1.1 CITY AMENDMENTS TO |
| | FBC. |
| | |
| | D) AREA CALCULATIONS TABLE INDICATES "ADDITION". |
| | ENGINEER TO CLARIFY WHERE IS THE ADDITION. CALCULATIONS |
| | SAYS EVERYTHING IS EXISTING. SEC. 106.1.1 CITY |
| | AMENDMENTS TO FBC. |
| | |
| | 4- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 |
| | FLORIDA STATUTE. |
| | ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK |
| | UP. |
| | |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561)805-6712 |