| Plan Review Notes For Permit 11040457 |
| Permit Number |
11040457 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-04-20 11:45:56 | PASS PROVISO | | | REFER TO SECTION 602.2.1 2007 FBC (M) DUCT DETECTORS . | | | SHALL BE INSTALLED IN THE SUPPLY DUCT. | | | REFER TO SECTION 606.3 INSTALLATION. 2007 FBC (M) THE | | | REQUIRED DUCT DETECTOR SHALL BE INSTALLED TO MONITOR | | | THE ENTIRE AIR FLOW CONVEYED BY THE SYSTEM. | | | REFER TO NFPA 90-A ACCESS TO DUCT DETECTORS .ACCESS | | | DOORS IN DUCT SHALL BE TIGHT FITTING AND SUITABLE | | | FOR THE REQUIRED DUCT CONSTRUCTION. | | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 | | | |
|