| Plan Review Notes For Permit 11040448 |
| Permit Number |
11040448 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-04-18 16:49:04 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. THE ASSEMBLY SELECTED FOR THE FLAT DECK IS DESIGNED | | | FOR MAXIMUM PRESSURE OF -60PSF. ENHANCED FASTENING IS | | | TO BE SPECIFIED BY AN ARCHITECT, ENGINEER, OR | | | REGISTERED ROOF CONSULTANT, SEE GENERAL LIMITATION #7 | | | ON THE PRODUCT APPROVAL. | | | | | | 2. PROVIDE THE MEAN ROOF HEIGHT (INFORMATION REQUIRED | | | TO DETERMINE DESIGN PRESSURES), FBC R301. THIS CAN BE | | | PROVIDED EITHER ON THE PLAN OR IN THE PROJECT | | | DESCRIPTION ON THE APPLICATION. | | | | | | |
|