Plan Review Notes
Plan Review Notes For Permit 11040441
Permit Number 11040441
Review Stop B
Sequence Number 1
Notes
Date Text
2011-04-21 14:53:29****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB.
  
 2. SEE OPENING 1. THE SIZE EXCEEDS THE MAX SIZE
 ALLOWED, SEE PRODUCT APPROVAL. PLEASE NOTE THAT WINDOW
 SIZES ARE ALWAYS SPECIFIED AS WIDTH X HEIGHT. IF
 MULLIONS ARE USED, SHOW ON THE FLOOR PLAN AND INCLUDE
 MULLION PRODUCT APPROVALS.
  
 3. REVISE THE FLOOR PLAN TO SHOW ROOM DESIGNATIONS.
 NOTE EXISTING CONDITIONS (TYPE OF WINDOW WHICH IS
 EXISTING, SUCH AS AWNING OR CASEMENT) FOR BEDROOMS, FBC
 R310, FBC EB 604.1. COMPLIANCE WITH EMERGENCY MEANS OF
 ESCAPE REQUIREMENTS CANNOT BE DETERMINED.
  