 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PER LOCAL POLICY, DUCT SMOKE DETECTORS SHALL INITIATE A
 GENERAL FIRE ALARM CONDITION.
  
 PROVIDE A PRE-RECORDED FIRE ALARM EVACUATION MESSAGE
 INSTRUCTING OCCUPANTS AN EMERGENCY HAS BEEN REPORTED,
 LOCATE THE NEAREST EXIT AND EXIT THE BUILDING
 IMMEDIATELY.
  
 ALL MANUAL PULL STATIONS ARE ASSIGNED IDENTICAL
 ADDRESSES ON THE RISER DETAIL.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW