2011-04-20 13:00:00BUILDING PROVISO:
 PROVIDE AT TIME OF INSPECTION SOUND PROOFING
 DOCUMENTATION.
 2007/09 FBC-B 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES
 BETWEEN DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A
 PUBLIC OR SERVICE
 AREA WITHIN THE STRUCTURE SHALL HAVE AN IMPACT
 INSULATION CLASS (IIC)
 RATING OF NOT LESS THAN 50 (45 IF FIELD TESTED) WHEN
 TESTED IN ACCORDANCE
 WITH ASTM E 492.
  