| Plan Review Notes For Permit 11040307 |
| Permit Number |
11040307 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-05-16 16:05:17 | RESIDENTIAL (R3) ADDITION MECHANICAL REVIEW CHECKLIST. | | | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. | | | | | | 1- TRANSFER DUCTWORK SIZE FOR THE BALANCED RETURN AIR | | | DON'T COMPLY WITH THE BALANCED RETURN AIR EXCEPTION #1 | | | OF SEC. M1602.4. REVISE TRANSFER DUCT SIZE TO COMPLY | | | WITH THE ONE AND ONE HALF TIMES THE CROSS SECTIONAL | | | AREA OF THE SUPPLY DUCT ENTERING EACH ROOM. | | | | | | 2- A/C PLANS HAVE THE TITLE BLOCK OF THE ARCHITECT. | | | ARCHITECT NEEDS TO SIGN AND SEAL THIS PLAN AS REQUIRED | | | BY CHAPTER 481 FLORIDA STATUTE. WHEN THERE IS NOT | | | ARCHITECT'S TITLE BLOCK THE PLANS MAY BE SIGNED BY THE | | | LICENSED A/C CONTRACTOR APPLYING FOR THE PERMIT AS | | | REQUIRED BY THE BUILDING OFFICIAL. | | | | | | | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|