2011-05-16 16:05:17RESIDENTIAL (R3) ADDITION MECHANICAL REVIEW CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- TRANSFER DUCTWORK SIZE FOR THE BALANCED RETURN AIR
 DON'T COMPLY WITH THE BALANCED RETURN AIR EXCEPTION #1
 OF SEC. M1602.4. REVISE TRANSFER DUCT SIZE TO COMPLY
 WITH THE ONE AND ONE HALF TIMES THE CROSS SECTIONAL
 AREA OF THE SUPPLY DUCT ENTERING EACH ROOM.
  
 2- A/C PLANS HAVE THE TITLE BLOCK OF THE ARCHITECT.
 ARCHITECT NEEDS TO SIGN AND SEAL THIS PLAN AS REQUIRED
 BY CHAPTER 481 FLORIDA STATUTE. WHEN THERE IS NOT
 ARCHITECT'S TITLE BLOCK THE PLANS MAY BE SIGNED BY THE
 LICENSED A/C CONTRACTOR APPLYING FOR THE PERMIT AS
 REQUIRED BY THE BUILDING OFFICIAL.
  
  