Plan Review Notes
Plan Review Notes For Permit 11040307
Permit Number 11040307
Review Stop E
Sequence Number 1
Notes
Date Text
2011-04-26 12:02:05REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE DETECTORS IF THEY DO NOT
 ALREADY EXIST WITHIN THE RESIDENCE. IF THE RESIDENCE
 HAS GAS APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE
 A CARBON MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET
 OF EACH ROOM USED FOR SLEEPING. FBC R313
 SMOKE DETECTORS REQUIRED FOR NEW BEDROOM. FBC R 313
 OUTDOOR LIGHT AND INTERIOR WALL SWITCH REQUIRED AT NEW
 EXTERIOR DOOR. NEC 210.70 (A)(2).
 ALL NEW GENERAL PURPOSE OUTLETS INCLUDING THOSE IN THE
 BEDROOMS AND SMOKE ALARMS MUST BE AFCI PROTECTED. NEC
 210.12
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
 ADDITIONAL RECEPTACLE REQUIRED ADJACENT TO CLOSET. NEC
 210.52 (A)(2).
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  