| Plan Review Notes For Permit 11040307 |
| Permit Number |
11040307 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-04-26 12:02:05 | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO | | | INCLUDE INTERCONNECTED SMOKE DETECTORS IF THEY DO NOT | | | ALREADY EXIST WITHIN THE RESIDENCE. IF THE RESIDENCE | | | HAS GAS APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE | | | A CARBON MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET | | | OF EACH ROOM USED FOR SLEEPING. FBC R313 | | | SMOKE DETECTORS REQUIRED FOR NEW BEDROOM. FBC R 313 | | | OUTDOOR LIGHT AND INTERIOR WALL SWITCH REQUIRED AT NEW | | | EXTERIOR DOOR. NEC 210.70 (A)(2). | | | ALL NEW GENERAL PURPOSE OUTLETS INCLUDING THOSE IN THE | | | BEDROOMS AND SMOKE ALARMS MUST BE AFCI PROTECTED. NEC | | | 210.12 | | | NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11 | | | ADDITIONAL RECEPTACLE REQUIRED ADJACENT TO CLOSET. NEC | | | 210.52 (A)(2). | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|