| Date |
Text |
| 2011-05-16 13:47:37 | RESIDENTIAL (R3) ADDITION, BUILDING REVIEW CHECKLIST. |
| | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. |
| | |
| | 1- ACCORDING TO SEC. R301.2.1.4.3 OF 2009 REVISIONS |
| | THIS PROPERTY IS LOCATED ON EXPOSURE "C" NOT "B". |
| | REVISE THE DESIGN BASIS AND DOORS AND WINDOWS DESIGN |
| | PRESSURES ON SHEET A-1.01. |
| | ***NOTE: DOORS AND WINDOWS DESIGN PRESSURES SHOWN ON |
| | THE FLOOR PLAN DON'T CORRESPOND TO THE DESIGN PRESSURES |
| | SHOWN ON THE COMPONENTS AND CLADDING TABLE BY THE |
| | DESIGN BASIS AREA. REVISE AS REQUIRED TO MATCH. |
| | |
| | 2- VALUE DECLARED IN THE PERMIT APPLICATION IS TOO LOW. |
| | SEC. 108.3 CITY AMENDMENTS TO FBC. PERMIT APPLICATION |
| | SAYS $3000. DO YOU MEAN $30,000?. VALUATION WAS CHANGED |
| | TO $30,000. THIS WILL COVER ALL THE SCOPE OF WORK SHOWN |
| | ON PLANS. PERMIT FEES WILL BE ADJUSTED ACCORDINGLY. |
| | |
| | 3- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH |
| | COUNTY. (2300 N JOG RD) TO VERIFY IF IMPACT FEES ARE |
| | DUE. BRING BACK STAMPED PLANS AND COPY OF PAID RECEIPT |
| | IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF THE |
| | UNIFIED LAND DEVELOPMENT CODE. |
| | |
| | 4- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 |
| | FLORIDA STATUTE. |
| | ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK |
| | UP. |
| | |
| | 5- LESS THAN 4:12 ROOF PITCH REQUIRES 2 LAYERS OF |
| | UNDERLAYMENT. SEC. R905.2.2. SPECIFY ON PLANS REQUIRED |
| | UNDERLAYMENT. |
| | |
| | 6- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9B-72 FOR: |
| | A) ROOF SHINGLES. |
| | |
| | B) CASEMENT WINDOWS. NOA 08-0709.16 SUBMITTED IS FOR |
| | PROJECTED WINDOWS NOT FOR CASEMENT WINDOWS. ALSO, THIS |
| | NOA DOESN'T MATCH NOA SPECIFIED BY THE ARCHITECT ON |
| | FLOOR PLAN ON SHEET A-1.01. |
| | |
| | C) ALL STRUCTURAL SIMPSON CONNECTORS SPECIFIED ON PLANS |
| | AND DETAILS. PROVIDE ONLY THE COVER PAGE AND PAGE |
| | SHOWING SPECIFIED CONNECTOR. |
| | |
| | 7- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC. |
| | |
| | 8- SPECIFY CARBON MONOXIDE ALARMS ON PLANS AS REQUIRED |
| | BY SEC. R313.4 OF 2009 REVISIONS. |
| | |
| | 9- ARCHITECT TO REVISE THE NORTH ARROW ORIENTATION ON |
| | SHEET A-1.01 TO MATCH SURVEY. ENERGY CALCULATIONS |
| | ORIENTATION NEED TO BE REVISED BECAUSE THEY ARE BASED |
| | ON THE NORTH ARROW ORIENTATION SPECIFIED ON PLANS. |
| | |
| | 10- ENERGY CALCULATIONS. A) REVISE ENERGY CALCULATIONS |
| | TO MATCH REVISED BUILDING ORIENTATION. SEE ITEM #9 |
| | ABOVE. REVISE WINDOWS AND WALLS ORIENTATION. |
| | |
| | B) THERE IS NOT GARAGE ON THIS BUILDING. SEE PLANS. |
| | REVISE AS REQUIRED. |
| | |
| | 11- SHEET A-1.01: |
| | |
| | A) SPECIFY SIZE OF BEDROOM EGRESS WINDOWS TO VERIFY |
| | COMPLIANCE WITH SEC. R310. |
| | |
| | B) PLYWOOD SHEATHING NAILING SCHEDULE: * NEED TO |
| | SPECIFY 8D RING SHANK NAILS FOR ROOF ZONES 2 AND 3 |
| | ALSO. ** REVISE NOTE REGARDING NO RING SHANK NAILS |
| | REQUIRED IF MEAN ROOF HEIGHT IS LESS THAN 25'. RING |
| | SHANK NAILS ARE REQUIRED IN ALL ROOF ZONES. SEC. |
| | R803.2.3.1. *** GABLE END ROOF ZONE IS 5' MIN. SEE |
| | FIGURE R803.2.3.1. SPECIFY ON PLANS. |
| | |
| | C) SPECIFY SIZE OF BOND BEAM AND CLARIFY LOCATION AND |
| | NUMBER OF REINFORCEMENT BARS. WALL SECTIONS SHOW 2 BARS |
| | ON TOP AND TWO BARS AT BOTTOM. CLARIFY DETAILS. SEC. |
| | 106.1.1 CITY AMENDMENTS TO FBC. |
| | |
| | D) GABLE END DETAIL C/A-1.01: SPECIFY HOW MUCH |
| | EMBEDMENT IS REQUIRED FOR THE 1/2" ANCHOR BOLT THAT IS |
| | FASTENING THE 2X8 PLATE. SEC. 106.1.1 CITY AMENDMENTS |
| | TO FBC. |
| | |
| | E) GABLE END DETAIL C/A-1.01 SPECIFIES 2X4 OUTRIGGERS |
| | AT 24"O.C. WHILE ROOF FRAMING PLAN SPECIFIES 2X4 |
| | OUTRIGGERS AT 12"O.C. REVISE AS REQUIRED TO MATCH. SEC. |
| | 106.1.1 CITY AMENDMENTS. |
| | |
| | F) TYP EXTERIOR WALL DETAIL B/1-1.01: CLARIFY STUCCO |
| | FINISH DISTANCE FROM FINISH GRADE. SEE SEC. R704 |
| | REGARDING TERMITES INSPECTIONS AND REVISE AS REQUIRED. |
| | |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561)805-6712 |