| Notes |
| Date |
Text |
| 2011-05-19 13:38:55 | 332 EVERNIA STREET | | | PERMIT NUMBER 11040302 | | | "INTERIOR RENOVATIONS" | | | | | | | | | 1. REVISION CLOUD ON SHEET A-1 FOR HARDWARE NOTES IS | | | INCORRECT AND MISLEADING. DOORS SUBJECT TO AN OCCUPANT | | | LOAD OF 100 OR MORE MUST BE EQUIPPED WITH PANIC | | | HARDWARE WITH NO OTHER LOCKS OR LATCHES. IN REVIEW OF | | | SECTION 12.2.2.2.4 (2) NEW ASSEMBLY OCCUPANCIES "ANY | | | LATCHING DEVICES ON SUCH DOORS FROM AN ASSEMBLY | | | OCCUPANCY HAVING AN OCCUPANT LOAD OF 100 OR MORE ARE | | | RELEASED BY PANIC HARDWARE OR FIRE EXIT HARDWARE". ON | | | MAY 19, 2011, THIS WRITER SPOKE TO ARCHITECT JEFFREY | | | GASPSTUR BY TELEPHONE REGARDING THIS MATTER. | | | | | | 2. BATHROOM DOORS CANNOT SWING TOO FAR INTO EXIT ACCESS | | | CORRIDOR. THIS INFORMATION WAS PREVIOUSLY PROVIDED BY | | | THE FIRE PLAN REVIEWER. | | | | | | | | | APPROVED PROVISO | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION |
|