2011-05-03 10:14:47332 EVERNIA STREET
 PERMIT #11040302
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE PERMIT APPLICATION INDICATES NO CHANGE IN OCCUPANCY
 (ASSEMBLY). RECORDS INDICATE THIS LOCATION WAS
 PREVIOUSLY A FURNITURE STORE (MERCANTILE).
  
 DESIGN SHALL CONFORM TO THE FLORIDA FIRE PREVENTION
 CODE 2007 EDITION (NFPA 1 & NFPA 101 - 2006 EDITION
 WITH FLORIDA AMENDMENTS).
  
 PROVIDE BUILDING ADDRESS VISIBLE FROM THE STREET.
 NUMBERS SHALL BE AT LEAST SIX-INCHES IN HEIGHT AND
 SHALL CONTRAST THE BACKGROUND (REFERENCE: SECTION
 10.12.1.2 OF THE FLORIDA FIRE PREVENTION CODE - NFPA
 1).
  
 PORTABLE FIRE EXTINGUISHERS SHALL HAVE A MINIMUM RATING
 OF 2A:10BC AND SHALL BE TAGGED BY A LICENSED FIRE
 EXTINGUISHER COMPANY.
  
 PROVIDE EXISTING EGRESS DOOR LOCK INFORMATION. NOTE: IF
 DOORS ARE EQUIPPED WITH A LATCH, ASSEMBLY OCCUPANCIES
 WITH AN OCCUPANT LOAD EXCEEDING 100 PERSONS SHALL HAVE
 EGRESS DOOR LATCHES RELEASED BY PANIC HARDWARE.
  
 THE LAVATORY DOORS OBSTRUCT THE CORRIDOR. DURING ITS
 SWING, ANY DOOR IN A MEANS OF EGRESS SHALL NOT LEAVE
 LESS THAN ONE-HALF OF THE REQUIRED WIDTH OF A CORRIDOR
 UNOBSTRUCTED AND SHALL NOT PROJECT MORE THAN 7 INCHES
 INTO THE REQUIRED WIDTH OF A CORRIDOR WHEN THE DOOR IS
 FULLY OPEN.
  
 PROVIDE RAMP AND HANDRAIL DETAILS. RAMP IS REQUIRED TO
 HAVE A LANDING AT THE BOTTOM PER SECTION 7.2.5.3.2.1 OF
 THE FLORIDA FIRE PREVENTION CODE (NFPA 101). HANDRAILS
 ARE REQUIRED WITHIN 30 INCHES OF ALL PORTIONS OF RAMP
 EGRESS WIDTH.
  
 PROVIDE TACTILE SIGNAGE AT ALL EXIT DOORS HAVING EXIT
 SIGNS.
  
 POST BUILDING OCCUPANT LOAD NEAR FRONT ENTRANCE DESK.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  