| Plan Review Notes For Permit 11040302 |
| Permit Number |
11040302 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-04-19 09:39:08 | FBC PLUMBING 2007 REVIEW #1 | | | DENNIED: | | | | | | 1. FBC 106.3.5.1.3 PLUMBING MINIMUM REVIEW CRITERIA- | | | HOT AND COLD WATER DIAGRAM AND WATER HEATER REQUIRED ON | | | PLAN. | | | | | | 2. DRINKING FOUNTAINS ARE NOT SHOWN ON RISER DIAGRAM. | | | | | | 3. THE WATER CLOSET SHOWN ATTACHED TO THE BUILDING | | | DRAIN IS NOT VENTED. | | | | | | 4. 1002.4 TRAP PRIMERS ARE REQUIRED FOR FLOOR DRAINS. | | | | | | **** NOTE **** | | | PLUMBING NOTE #7 AIR CHAMBERS ARE NO LONGER PART OF | | | PLUMBING CODE. WATER HAMMER ARRESTORS ARE TO BE | | | INSTALLED WHERE REQUIRED. | | | | | | REVIEW BY LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | (561) 805-6692 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] | | | |
|