| Plan Review Notes For Permit 11040293 |
| Permit Number |
11040293 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-04-12 15:45:52 | 2465 MERCER AVENUE, SUITE #101 | | | PERMIT #11040293 | | | MASTER #11030091 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | PROVIDE A RISER OR WIRING DIAGRAM TO INCLUDE ALL NEW OR | | | RELOCATED APPLIANCES. INDICATE THE ADDRESSES OF THE | | | INITIATING DEVICES TO BE ADDED TO THE SYSTEM. | | | | | | PROVIDE ADDITIONAL BATTERY CALCULATION INFORMATION AS | | | THE CALCULATION SUBMITTED ONLY REFLECTS THE DRAW OF THE | | | MAIN CONTROL PANEL. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW |
|