| Plan Review Notes For Permit 11040263 |
| Permit Number |
11040263 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-04-22 13:55:27 | **PROVISO** | | | | | | 1. SOME ROOMS WITH FULL-HEIGHT PARTITIONS DO NOT HAVE | | | TRANSFER DUCTS OR OTHER MEANS BY WHICH RETURN AIR CAN | | | GET BACK TO THE CENTAR AIR HANDLER. EXAMPLE: COFFEE | | | ROOM 405. THIS IS JUST AN EXAMPLE. CHECK ALL AREAS AND | | | PROVIDE BALANCED RETURN PER FBC-M 601.4. REVISION | | | REQUIRED. | | | | | | 2. SEVERAL ROOMS HAVE TRANSFER DUCTS WHICH ARE NOT | | | SIZED TO MEET THE BALANCED RETURN EXCEPTIONS UNDER | | | FBC-M 601.4. EXAMPLES: ROOMS 409 AND 453. PLEASE CHECK | | | ALL AREAS AND PROVIDE BALANCED RETURN PER FBC-M 601.4. | | | REVISION REQUIRED. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|