 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****APPROVED WITH PROVISIONS*****
  
 SHEET LS1.0 THE DELAYED EGRESS FEATURE ON THE ELEVATOR
 LOBBY DOOR SHALL NOT RELOCK AUTOMATICALLY. AFTER THE
 LOCK HAS BEEN RELEASED, RELOCKING SHALL BE BY MANUAL
 MEANS ONLY PER NOTE 4D OF SECTION 7.2.1.6.1. VERIFY THE
 SWING OF THIS DOOR AS IT IS NOTED PULL TO OPEN;
 HOWEVER, THE DOOR APPEARS TO REQUIRE A PUSHING MOTION
 TO OPEN ON THE PLAN.
  
 SHEET A1.0 DOORS ARE REQUIRED TO SWING IN THE DIRECTION
 OF TRAVEL WHEN THE ROOM SERVES 50 OR PERSONS SUCH AS
 CONFERENCE ROOM 1.
  
 SHEET A2.0 ELIMINATE STORAGE WITHIN 18 INCHES OF
 CEILINGS AND SPRINKLER DEFLECTORS.
  
 SHEET FA0.1 ACTIVATION OF A DUCT SMOKE DETECTOR SHALL
 INITIATE A GENERAL FIRE ALARM CONDITION.
  
 SHEET FA2.1 PROVIDE NOTIFICATION APPLIANCE IN ROOM/AREA
 405, 439, 440, 441 AND 443.
  
 SHEET FS2.1 SHOP DRAWINGS AND HYDRAULIC CALCULATIONS
 SHALL NOT BE SEALED BY THE CONTRACTOR AS THE ENGINEER
 OF RECORD IS ALREADY ESTABLISHED BY THE CONSTRUCTION
 DOCUMENTS. PER FLORIDA ADMINISTRATIVE CODE, CHAPTER
 61G15-32.002, THE FLORIDA REGISTERED PROFESSIONAL
 ENGINEER WHO DEVELOPS THE FIRE PROTECTION SYSTEM DESIGN
 CRITERIA AND SEALS THE CONSTRUCTION DOCUMENTS IS DEEMED
 THE ENGINEER OF RECORD.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  