| 2011-07-08 14:17:25 | BUILDING PROVISO | | | | | | 1) SUBMIT TWO SETS OF WALL DETAILS THAT SPECIFY THE | | | FILE NUMBER OR DESIGN NUMBER OF THE ONE HOUR FIRE-RATED | | | SEPARATION WALL BETWEEN THE TWO UNITS. ANSI/UL 263 IS | | | THE TEST METHOD AND ACCEPTANCE CRITERIA. | | | | | | 2) SUBMIT TWO SETS OF CORRECTED ENERGY CALCULATIONS. | | | THE ONES THAT WERE SUBMITTED ARE INCORRECT. THE NUMBER | | | OF WINDOWS AND DOORS IN EACH UNIT ARE INCORRECT. THE | | | PLANS SHOW A GABLE ROOF NOT A HIP. THIS COMMENT WAS | | | UNDER MECHANICAL REVIEW IN THE FIRST REVIEW. THE FORM | | | DOES NOT SPECIFY TWO UNITS. THE COMMON WALL BETWEEN THE | | | TWO UNITS IS NOT LISTED ON THE FORM. THERE ARE ONLY TWO | | | DOORS AND THE FORM LISTS THREE. THE FORM ONLY LISTS 8 | | | WINDOWS AND THE ELEVATION PLANS SHOW 14. | | | | | | 3) THE PRODUCT APPROVALS THAT WERE SUBMITTED ARE FOR | | | NON-IMPACT RATED WINDOWS. IMPACT PROTECTION IS REQUIRED | | | BY FBC R301.2.1.2 AND FBC EXISTING BUILDING 606.4. | | | UNLESS THERE ARE EXISTING STORM PANELS, SUBMIT TWO | | | COPIES OF PRODUCT APPROVALS AND AN INSTALLATION | | | SCHEDULE FOR THE STORM PANELS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|