| Plan Review Notes For Permit 11040253 |
| Permit Number |
11040253 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-05-13 16:05:04 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY BUILDING | | | | | | 1) SUBMIT DETAIL OF THE ONE HOUR FIRE-RATED SEPARATION | | | WALL INCLUDE THE FILE NUMBER FOR THE TESTED ASSEMBLY | | | BEING USED. SHOW COMPLIANCE WITH FBC R317.1 WHICH | | | REQUIRES THE WALL TO EXTEND TO THE UNDERSIDE OF THE | | | ROOF SHEATHING. | | | | | | 2) THE STRUCTURE IS LOCATED IN A SPECIAL FLOOD HAZARD | | | AREA "A-9" BFE 13'. ALL NEW EQUIPMENT SERVICING THE | | | DWELLINGS WILL BE REQUIRED TO BE 6" ABOVE THE BASE | | | FLOOD ELEVATION WHICH IS A MINIMUM OF 13'-6". | | | | | | 3) THE PLANS HAVE AN AREA TABULATION THAT INDICATE 3 | | | UNITS AND THERE ARE ONLY 2 UNITS SHOWN. TO AVOID | | | CONFUSION PLEASE REVISE. NOTE: PERMIT #09080470 TO | | | CONVERT THIS STRUCTURE FROM 3 UNITS TO 2 WAS ISSUED AND | | | NEVER COMPLETED. | | | | | | 4) THERE WAS WORK DONE UNDER EXPIRED PERMIT # 09080470 | | | THAT WAS NOT INSPECTED. THESE ISSUES WILL NEED TO BE | | | ADDRESSED BEFORE A NEW PERMIT CAN BE ISSUED. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|