| Plan Review Notes For Permit 11040215 |
| Permit Number |
11040215 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-04-08 13:56:58 | 501 SOUTH FLAGLER DRIVE, SUITE #502 | | | PERMIT #11040215 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | *****APPROVED WITH PROVISIONS***** | | | | | | DEMOLITION WORK TO COMPLY WITH THE REQUIREMENTS OF NFPA | | | 241. DEBRIS SHALL BE REMOVED DAILY. | | | | | | THE NEW SIDE LIGHT GLAZING SHOWN ADJACENT TO THE SUITE | | | ENTRY DOOR APPEARS TO BE LOCATED IN A FIRE RATED | | | CORRIDOR WALL. VERIFY GLAZING IS FIRE RATED. | | | | | | NEW WALLS AND CEILING CONFIGURATION WILL AFFECT FIRE | | | SPRINKLER AND FIRE ALARM LAYOUT. SEPARATE PLANS AND | | | PERMITS ARE REQUIRED FOR THE INSTALLATION/MODIFICATION | | | OF THESE SYSTEMS. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW |
|