 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****APPROVED WITH PROVISIONS*****
  
 DEMOLITION WORK TO COMPLY WITH THE REQUIREMENTS OF NFPA
 241. DEBRIS SHALL BE REMOVED DAILY.
  
 THE NEW SIDE LIGHT GLAZING SHOWN ADJACENT TO THE SUITE
 ENTRY DOOR APPEARS TO BE LOCATED IN A FIRE RATED
 CORRIDOR WALL. VERIFY GLAZING IS FIRE RATED.
  
 NEW WALLS AND CEILING CONFIGURATION WILL AFFECT FIRE
 SPRINKLER AND FIRE ALARM LAYOUT. SEPARATE PLANS AND
 PERMITS ARE REQUIRED FOR THE INSTALLATION/MODIFICATION
 OF THESE SYSTEMS.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW