| Plan Review Notes For Permit 11040205 |
| Permit Number |
11040205 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2011-06-09 14:17:41 | BUILDING REVIEW APPROVED WITH PROVISO | | | | | | 1- A) REVISE SURVEY TO STATE FLOOD ZONE "A". | | | B) PROVIDE SURVEY WITH ORIGINAL SIGNATURE. CHAPTER 472 | | | FLORIDA STATUTES. | | | | | | 2- PROVIDE PRODUCT APPROVAL FOR: A) DECORATIVE SHUTTERS | | | SHOWN ON EXTERIOR ELEVATIONS. AND, PROVIDE COMPLETE | | | INSTALLATION SCHEDULE. | | | B) SINGLE HUNG WINDOWS THAT MEET THE CALCULATED DESIGN | | | PRESSURES. SEE SHEET S1. | | | | | | ***NOTE: ARCHITECT TO REVIEW ALL PRODUCT APPROVALS. | | | | | | 3- CLEARLY SPECIFY ATTIC LIVE LOAD. SEE TABLE R301.5. | | | | | | 4- PROVIDE COMPLETE INFORMATION FOR BALCONY RAILING. | | | SEC. R312. | | | | | | 5- ENERGY CALCULATIONS CALL FOR UNVENTED ATTIC. SHEET | | | S3 SHOW ATTIC VENTILATION CALCULATIONS. REVISE AS | | | REQUIRED TO MATCH AND PROVIDE REQUIRED SPECIFICATIONS. | | | | | | 6- REVISE ELEVATION CERTIFICATES. FLOOD ZONE A NOT B. | | | AND NEED ORIGINAL SIGNATURES. GIVE THEM TO INSPECTOR. |
|