Plan Review Notes For Permit 11040205
Permit Number 11040205
Review Stop E
Sequence Number 1
Notes
Date Text
2011-04-11 11:43:09LOCATE EXISTING SERVICE, MAIN DISCONNECTS AND PANELS ON
 THE FLOOR PLAN. PROVIDE AN ELECTRICAL RISER DIAGRAM FOR
 THE EXISTING SERVICE. NEC 110.26
 RECEPTACLES SHALL BE TAMPER RESISTANT. NEC 406.11
 ALL NEW RECEPTACLES WITHIN THE DWELLING SHALL BE
 PROTECTED BY A LISTED ARC-FAULT CIRCUIT INTERRUPTER.
 NEC 210-12 (B)
 SUMMARIZE THE ELECTRICAL LOAD TO VERIFY THE EXISTING
 CAPACITY IS SUFFICIENT FOR THE NEW BATH AND BEDROOM.
 NEC 220
  