| 2011-04-11 11:43:09 | LOCATE EXISTING SERVICE, MAIN DISCONNECTS AND PANELS ON | | | THE FLOOR PLAN. PROVIDE AN ELECTRICAL RISER DIAGRAM FOR | | | THE EXISTING SERVICE. NEC 110.26 | | | RECEPTACLES SHALL BE TAMPER RESISTANT. NEC 406.11 | | | ALL NEW RECEPTACLES WITHIN THE DWELLING SHALL BE | | | PROTECTED BY A LISTED ARC-FAULT CIRCUIT INTERRUPTER. | | | NEC 210-12 (B) | | | SUMMARIZE THE ELECTRICAL LOAD TO VERIFY THE EXISTING | | | CAPACITY IS SUFFICIENT FOR THE NEW BATH AND BEDROOM. | | | NEC 220 | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | | | | |
|