| 2011-05-13 16:08:50 | RESIDENTIAL (R3) ADDITION, BUILDING REVIEW CHECKLIST. |
| | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. |
| | |
| | 1- PROVIDE ENERGY CALCULATIONS. SEC. N1100.3 OF CHAPTER |
| | 13 OF 2007 FLORIDA RESIDENTIAL CODE. |
| | |
| | 2- PER CONVERSATION WITH BUILDING OFFICIAL (DOUG WISE) |
| | THE PROPERTY IS LOCATED IN FLOOD ZONE A5 WITH A FLOOD |
| | BASE ELEVATION OF 7'-0". PROVIDE SURVEY SHOWING THE |
| | HOUSE FINISH FLOOR ELEVATION. IF THE HOUSE FINISH FLOOR |
| | ELEVATION IS LESS THAN 7'-6", THEN THE HOUSE WILL NEED |
| | TO BE RAISED. SEC. 94-541 CITY FLOOD PLAIN MANAGEMENT |
| | POLICY. |
| | |
| | 3- SHEET A1: CLARIFY HOW DO YOU ENTER THE SITTING ROOM. |
| | THERE ARE NO DOORS. SEC. 106.1.1 CITY AMENDMENTS TO |
| | FBC. |
| | |
| | 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9B-72 FOR: |
| | A) DECORATIVE SHUTTERS SHOWN ON EXTERIOR ELEVATIONS. |
| | AND, PROVIDE COMPLETE INSTALLATION SCHEDULE. |
| | |
| | B) COPPER CLADDING OVER ENTRY ROOF. SEE DETAIL 7/A5 ON |
| | SHEET A5. |
| | |
| | C) MODIFIED BITUMEN MEMBRANE ON SECOND FLOOR BALCONY. * |
| | THERE ARE TWO DIFFERENT PRODUCT APPROVALS SUBMITTED. |
| | PROVIDE ONLY ONE PRODUCT APPROVAL AND MAKE SURE PRODUCT |
| | APPROVAL IS FOR MODIFIED BITUMEN TO RECEIVE TILE AS |
| | SPECIFIED ON FLOOR PLAN 1/A1 ON SHEET A1. ** SPECIFY |
| | WHICH APPROVED ASSEMBLY IS GOING TO BE USED. *** |
| | PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS IF |
| | REQUIRED BY NOA SUBMITTED. |
| | |
| | D) SINGLE HUNG WINDOWS. FLORIDA PRODUCT APPROVAL |
| | FL9108-R0 SUBMITTED IS FOR 2004 CODE. NEED TO PROVIDE |
| | ONE FOR 2007 CODE. |
| | |
| | 5- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | ALL PRODUCT APPROVALS. SEC. 106.3.3 CITY AMENDMENTS TO |
| | FBC. |
| | |
| | 6- SECTION 2/A2 ON SHEET A2: CLARIFY FINISH GRADE |
| | ELEVATION TO VERIFY COMPLIANCE WITH WOOD DECAY SEC. |
| | R319.1(5). AND HEIGHT ABOVE FINISHED GRADE SEC. |
| | R404.1.6. AND, INSPECTION FOR TERMITES SEC. R704.1. |
| | DRAWING PROVIDE SHOWS STUCCO FINISH BELOW FINISH |
| | GRADE?. |
| | |
| | 7- SHEET S1: A) COMPONENTS AND CLADDING DESIGN |
| | PRESSURES ON THE WIND DESIGN CRITERIA INDICATES WORST |
| | CASE +/-64PSF. THIS DOESN'T MATCH THE DESIGN PRESSURES |
| | SHOWN ON THE 2 STORY SKETCH. REVISE AS REQUIRED. |
| | |
| | B) REVISE FLOOR DEAD LOADS SHOWN. 10PSF AT TOP AND |
| | 10PSF AT BOTTOM DON'T ADD UP TO 15PSF. |
| | |
| | C) SPECIFY AL THE LOADS INCLUDING THE ATTIC LIVE LOAD |
| | AND THE BALCONY LIVE LOAD AS REQUIRED BY TABLE R301.5. |
| | |
| | 8- SPECIFY ATTIC ACCESS SIZE AND LOCATION. SEC R807. |
| | |
| | 9- PROVIDE COMPLETE INFORMATION FOR BALCONY RAILING. |
| | SEC. R312. |
| | |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |