2011-05-13 16:08:50RESIDENTIAL (R3) ADDITION, BUILDING REVIEW CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- PROVIDE ENERGY CALCULATIONS. SEC. N1100.3 OF CHAPTER
 13 OF 2007 FLORIDA RESIDENTIAL CODE.
  
 2- PER CONVERSATION WITH BUILDING OFFICIAL (DOUG WISE)
 THE PROPERTY IS LOCATED IN FLOOD ZONE A5 WITH A FLOOD
 BASE ELEVATION OF 7'-0". PROVIDE SURVEY SHOWING THE
 HOUSE FINISH FLOOR ELEVATION. IF THE HOUSE FINISH FLOOR
 ELEVATION IS LESS THAN 7'-6", THEN THE HOUSE WILL NEED
 TO BE RAISED. SEC. 94-541 CITY FLOOD PLAIN MANAGEMENT
 POLICY.
  
 3- SHEET A1: CLARIFY HOW DO YOU ENTER THE SITTING ROOM.
 THERE ARE NO DOORS. SEC. 106.1.1 CITY AMENDMENTS TO
 FBC.
  
 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) DECORATIVE SHUTTERS SHOWN ON EXTERIOR ELEVATIONS.
 AND, PROVIDE COMPLETE INSTALLATION SCHEDULE.
  
 B) COPPER CLADDING OVER ENTRY ROOF. SEE DETAIL 7/A5 ON
 SHEET A5.
  
 C) MODIFIED BITUMEN MEMBRANE ON SECOND FLOOR BALCONY. *
 THERE ARE TWO DIFFERENT PRODUCT APPROVALS SUBMITTED.
 PROVIDE ONLY ONE PRODUCT APPROVAL AND MAKE SURE PRODUCT
 APPROVAL IS FOR MODIFIED BITUMEN TO RECEIVE TILE AS
 SPECIFIED ON FLOOR PLAN 1/A1 ON SHEET A1. ** SPECIFY
 WHICH APPROVED ASSEMBLY IS GOING TO BE USED. ***
 PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS IF
 REQUIRED BY NOA SUBMITTED.
  
 D) SINGLE HUNG WINDOWS. FLORIDA PRODUCT APPROVAL
 FL9108-R0 SUBMITTED IS FOR 2004 CODE. NEED TO PROVIDE
 ONE FOR 2007 CODE.
  
 5- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVALS. SEC. 106.3.3 CITY AMENDMENTS TO
 FBC.
  
 6- SECTION 2/A2 ON SHEET A2: CLARIFY FINISH GRADE
 ELEVATION TO VERIFY COMPLIANCE WITH WOOD DECAY SEC.
 R319.1(5). AND HEIGHT ABOVE FINISHED GRADE SEC.
 R404.1.6. AND, INSPECTION FOR TERMITES SEC. R704.1.
 DRAWING PROVIDE SHOWS STUCCO FINISH BELOW FINISH
 GRADE?.
  
 7- SHEET S1: A) COMPONENTS AND CLADDING DESIGN
 PRESSURES ON THE WIND DESIGN CRITERIA INDICATES WORST
 CASE +/-64PSF. THIS DOESN'T MATCH THE DESIGN PRESSURES
 SHOWN ON THE 2 STORY SKETCH. REVISE AS REQUIRED.
  
 B) REVISE FLOOR DEAD LOADS SHOWN. 10PSF AT TOP AND
 10PSF AT BOTTOM DON'T ADD UP TO 15PSF.
  
 C) SPECIFY AL THE LOADS INCLUDING THE ATTIC LIVE LOAD
 AND THE BALCONY LIVE LOAD AS REQUIRED BY TABLE R301.5.
  
 8- SPECIFY ATTIC ACCESS SIZE AND LOCATION. SEC R807.
  
 9- PROVIDE COMPLETE INFORMATION FOR BALCONY RAILING.
 SEC. R312.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712