| 2011-05-19 10:36:23 | 2007 FBC W/2009 REVISIONS |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) THE STRUCTURE IS LOCATED IN AN A5 FLOOD ZONE WITH A |
| | MINIMUM ELEVATION REQUIREMENT OF 7'-6" PER THE CITY OF |
| | WEST PALM BEACH CITY FLOOD PLAIN ORDINANCE ARTICLE |
| | XVII. THE GARAGE FLOOR ELEVATION IS REQUIRED TO BE A |
| | MINIMUM OF 7'-6" OR BE CONSTRUCTED WITH FLOOD DAMAGE |
| | RESISTANT MATERIALS AND FLOOD VENTS. FBC R323 |
| | |
| | 2) THE ENERGY CALCULATION FORM IS REQUIRED TO BE SIGNED |
| | AND DATED BY THE OWNER/AGENT. THERE ARE ALSO MISTAKES |
| | IN THE CALCULATIONS. SEE MECHANICAL REVIEW COMMENTS. |
| | FBC 13-103 |
| | |
| | 3) SUBMIT TWO COPIES OF THE SPECIFICATIONS FOR THE |
| | ICYNENE SPRAY FOAM INSULATION AND SPECIFY THE IGNITION |
| | BARRIER THAT WILL BE USED. FBC R314 |
| | |
| | 4) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR |
| | THE PROJECT PER CITY AMENDMENTS 106.3.3. |
| | |
| | 5) SPECIFY THE METHOD OF ATTACHMENT THAT WILL BE USED |
| | TO INSTALL THE CLAY ROOF TILE AND SUBMIT THE PRODUCT |
| | APPROVALS FOR IT. DCA RULE 9B-72 |
| | |
| | 6) SUBMIT TWO COPIES OF SIGNED AND SEALED RAS 117 |
| | CALCULATIONS FOR ENHANCED FASTENING OF THE BASE SHEET |
| | FOR THE GAF MODIFIED ROOFING MATERIAL AS REQUIRED BY |
| | LIMITATION # 7 OF THE PRODUCT APPROVAL. |
| | |
| | 7) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE |
| | OUT-SWING SERVICE DOOR AT THE GARAGE AS REQUIRED BY DCA |
| | RULE 9B-72. |
| | |
| | 8) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE |
| | SERIES "450" ALUMINUM DOOR HAS BEEN SUPERSEDED. PLEASE |
| | SUBMIT THE CURRENT NOA NO. 09-0723.04. |
| | |
| | 9) THE TRUSS DRAWINGS AND LAYOUT ARE REQUIRED TO BE |
| | REVIEWED BY THE DESIGNER OF RECORD FOR THE STRUCTURE. |
| | THE D.O.R. SHOULD STAMP THE LAYOUT WITH A SHOP DRAWING |
| | REVIEW STAMP. NOTE: THE TRUSS DRAWINGS AND LAYOUT FOR |
| | SINGLE FAMILY HOMES CAN BE GIVEN TO THE FIELD INSPECTOR |
| | AT THE TRUSS INSPECTION. |
| | |
| | 10) PROVIDE ROOF DRAIN AND OVERFLOW SCUPPER SIZING |
| | CALCULATIONS FOR THE BALCONY AS REQUIRED BY FBC R903.4 |
| | AND FBC 1106 & 1107. |
| | |
| | 11) TWO SETS OF SHOP DRAWINGS APPROVED BY THE DESIGNER |
| | OF RECORD FOR THE STRUCTURE FOR THE PRECAST HOLLOW CORE |
| | SLAB SYSTEM WILL BE REQUIRED TO BE SUBMITTED PRIOR TO |
| | INSTALLATION. |
| | |
| | 12) SUBMIT TWO SETS OF SPECIFICATIONS AND INSTALLATION |
| | INSTRUCTIONS FOR THE BUILT-IN BBQ ON THE COVERED PORCH. |
| | FBCR M1306.1 |
| | |