| 2011-04-27 10:00:14 | 1300 NORTH FLORIDA MANGO ROAD, SUITES 21 AND 21A |
| | PERMIT #11040155 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | |
| | SMOKE OR FIRE-RATED WALL/PARTITION SHALL BE PERMANENTLY |
| | IDENTIFIED WITH SIGNS OR STENCILING READING FIRE/SMOKE |
| | BARRIER PROTECT ALL OPENINGS. CHARACTERS SHALL BE AT |
| | LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN WIDTH. |
| | IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 FEET ON |
| | CENTER. REFERENCE SECTION 8.3.2.4 OF FLORIDA FIRE |
| | PREVENTION CODE NFPA 101 |
| | |
| | FOR ISSUANCE OF A GENERAL BUILDING PERMIT, SECTION |
| | 106.3.5 OF THE FLORIDA BUILDING CODE REQUIRES FIRE |
| | PROTECTION CONSTRUCTION DOCUMENTS FOR THE DESIGN OR |
| | ALTERATION OF THE FIRE SPRINKLER AND FIRE ALARM SYSTEM. |
| | SEPARATE PLANS AND PERMITS WILL ALSO BE REQUIRED FOR |
| | THE INSTALLATION OR MODIFICATION OF FIRE SPRINKLER AND |
| | FIRE ALARM SYSTEM. |
| | |
| | ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS |
| | OF NFPA 241. FIRE PROTECTION SYSTEMS ARE TO REMAIN |
| | ACTIVE DURING DEMOLITION AND RENOVATION. IF ANY FIRE |
| | PROTECTION SYSTEM IS INOPERABLE FOR MORE THAN 4 HOURS |
| | IN A 24 HOUR PERIOD, A FIRE WATCH IS REQUIRED. ALL FIRE |
| | WATCHES MUST BE REQUESTED IN WRITING AND SUBMITTED TO |
| | THE FIRE MARSHAL'S OFFICE. |
| | |
| | LIMITED INFORMATION HAS BEEN PROVIDED AND THE INTENDED |
| | USE IS NOT CLEAR FOR THE AREA LABELED AS "DISPLAY." |
| | PROVIDE FLOOR PLAN INFORMATION AS TO THE INTENDED |
| | LAYOUT FOR THE DISPLAY AREA. INDICATE WHAT TYPE OF |
| | ITEMS OR MATERIALS WILL BE DISPLAYED AND HOW THESE |
| | ITEMS WILL BE ARRANGED. |
| | |
| | WESLEY JOLIN |
| | WEST PALM BEACH FIRE RESCUE |
| | FIRE & LIFE SAFETY PLAN REVIEW |