2011-04-11 11:26:37FBC PLUMBING 2007 PLAN REVIEW #1
 DENIED:
  
 1. 106.3.5.1.3 PLUMBING MINIMUM PLAN REVIEW CRITERIA.
 WATER SUPPLY PIPING REQUIRED.
  
 2. SANITARY RISER DOES NOT INCLUDE THE MOP SINK
  
 3. 11-4.19.1 MINIMUM FOR ACCESSIBLE LAV. IS 15" FROM
 SIDE WALL.
  
 NOTE FOR THE FLOOR DRAINS- 1002.4 TRAP SEALS. WHERE A
 TRAP SEAL IS SUBJECT TO LOSS BY EVAPORATION, A TRAP
 SEAL PRIMER VALVE SHALL BE INSTALLED. A TRAP SEAL
 PRIMER VALVE SHALL CONFORM TO ASSE 1018 OR ASSE 1044.
  
 REVIEW BY LARRY WAGNER
 CHIEF PLUMBING INSPECTOR