| Plan Review Notes For Permit 11040155 |
| Permit Number |
11040155 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-04-11 11:26:37 | FBC PLUMBING 2007 PLAN REVIEW #1 | | | DENIED: | | | | | | 1. 106.3.5.1.3 PLUMBING MINIMUM PLAN REVIEW CRITERIA. | | | WATER SUPPLY PIPING REQUIRED. | | | | | | 2. SANITARY RISER DOES NOT INCLUDE THE MOP SINK | | | | | | 3. 11-4.19.1 MINIMUM FOR ACCESSIBLE LAV. IS 15" FROM | | | SIDE WALL. | | | | | | NOTE FOR THE FLOOR DRAINS- 1002.4 TRAP SEALS. WHERE A | | | TRAP SEAL IS SUBJECT TO LOSS BY EVAPORATION, A TRAP | | | SEAL PRIMER VALVE SHALL BE INSTALLED. A TRAP SEAL | | | PRIMER VALVE SHALL CONFORM TO ASSE 1018 OR ASSE 1044. | | | | | | REVIEW BY LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | (561) 805-6692 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] | | | |
|