| 2011-04-07 12:23:57 | 1300 NORTH FLORIDA MANGO ROAD, SUITES 21 AND 21A |
| | PERMIT #11040155 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | THE OCCUPANCIES INDICATED ON SHEET A1 ARE STORAGE AND |
| | BUSINESS; HOWEVER, THE OCCUPANT LOAD FACTOR OF 15 |
| | SQUARE FEET PER PERSON CORRELATES TO AN ASSEMBLY |
| | OCCUPANCY. INDICATE THE INTENDED USE OF THE SPACE. |
| | |
| | THE PROPOSED OCCUPANCY TYPES REQUIRE A ONE HOUR RATED |
| | FIRE SEPARATION BETWEEN DIFFERENT OCCUPANCIES. |
| | |
| | THE VESTIBULE DOOR SWING HINDERS FREE FLOWING EGRESS AT |
| | THE NORTHEAST EXIT. THIS UNRATED DOOR IS LOCATED IN A |
| | FIRE RATED WALL. |
| | |
| | PANIC HARDWARE IS REQUIRED ON DOORS IN ASSEMBLY |
| | OCCUPANCIES WITH AN OCCUPANT LOAD EXCEEDING 100 |
| | PERSONS.EACH NEW SMOKE OR FIRE-RATED WALL/PARTITION |
| | SHALL BE PERMANENTLY IDENTIFIED WITH SIGNS OR |
| | STENCILING READING FIRE/SMOKE BARRIER PROTECT ALL |
| | OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN |
| | HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE |
| | SPACED NOT MORE THAN 15 FEET ON CENTER. REFERENCE |
| | SECTION 8.3.2.4 OF FLORIDA FIRE PREVENTION CODE NFPA |
| | 101 |
| | |
| | FOR ISSUANCE OF A GENERAL BUILDING PERMIT, SECTION |
| | 106.3.5 OF THE FLORIDA BUILDING CODE REQUIRES FIRE |
| | PROTECTION CONSTRUCTION DOCUMENTS FOR THE DESIGN OR |
| | ALTERATION OF THE FIRE SPRINKLER AND FIRE ALARM SYSTEM. |
| | SEPARATE PLANS AND PERMITS WILL ALSO BE REQUIRED FOR |
| | THE INSTALLATION OR MODIFICATION OF FIRE SPRINKLER AND |
| | FIRE ALARM SYSTEM. |
| | |
| | PROVIDE TACTILE SIGNAGE AT EXITS UTILITIZING EXIT |
| | SIGNS. |
| | |
| | ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS |
| | OF NFPA 241. |
| | |
| | PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY |
| | RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING |
| | NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM |
| | WWW.KNOXBOX.COM. |
| | |
| | WESLEY JOLIN |
| | WEST PALM BEACH FIRE RESCUE |
| | FIRE & LIFE SAFETY PLAN REVIEW |