| 2011-04-14 15:30:31 | BUILDING PLAN REVIEW |
| | PERMIT: 11040155 |
| | ADD: 1300 N. FLORIDA MANGO RD |
| | CONT: MALASKY HOMES, INC |
| | TEL: (561)329-9428 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) SHEET A-1 DESIGN CRITERIA: |
| | |
| | 1A) PLANS INDICATE A S-2 STORAGE OCCUPANCY OF |
| | APPROXIMATELY 2400 SQ FT AND A BUSSINESS OCCUPANCY OF |
| | APPROXIMATELY 2200 SQ FT PLUS A ASSEMBLY OCCUPANCY OF |
| | 2400 SQ FT WHEN THE OCCUPANCY DATA IS TOTALED UP ADDING |
| | UP TO 7,000 SQ FT FOR THIS TENANT SPACE. IT APPEARS TO |
| | BE A DISCREPANCY IN SQUARE FOOTAGE FOR THIS TENANT |
| | SPACE. 106.1.2 ADDITIONAL INFORMATION REQUIRED? |
| | |
| | 1B) THE TENANT SPACE DOES NOT INDICATE ANY ASSEMBLY |
| | OCCUPANCY, THE PLAN DOES INDICATE A FLEX ROOM, |
| | INSTRUCTIONAL MEETING ROOM IS THIS TO BE CONSIDERED THE |
| | CONFERENCE ROOM? WHEN CALCULATING THE SQ FOOTAGE OF THE |
| | CONFERENCE ROOM OF 556 SQ FT / 15 = AN OCCUPANT LOAD OF |
| | 37 OCCUPANTS, PLEASE PROVIDE ADDITIONAL INFORMATION AS |
| | TO THE LOCATION OF AN ASSEMBLY OCCUPANCY, 106.1.2 |
| | ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 1C) THE PLANS CURRENTLY INDICATE WALLS TO BE REMOVED |
| | BUT THERE STILL SEAMS TO BE A A BUSINESS SUB-OCCUPANCY |
| | AND EITHER A WAREHOUSE (STORAGE S-2) OCCUPANCY OR |
| | MERCANTILE OCCUPANCY IN EITHER CASE THIS IS A MIXED |
| | OCCUPANCY (508.3). THE PLAN DOES NOT INDICATE IF THE |
| | DESIGN INCORPORATES SEPERATED ( 508.3.1.3) OR |
| | NON-SEPERATED OCCUPNCIES AS PER 508.3.2. THE BUSINESS |
| | OCCUPANCY IS CLEARLY OVER 10% OF THE SQ FT AREA. |
| | |
| | 2)THE PLANS SHOW ONE OF THE EXIT ROUTES GOING THROUGH A |
| | ROOM LABELED EXISTING FLEX SP? WHAT IS THE USAGE OF |
| | THIS ROOM, IS IT CONSIDERED A STORAGE ROOM? |
| | |
| | 3) IN THE NORTH EAST CORNER OF THE BUILDING THERE IS A |
| | EXIT TYPE VESTIBULE BOTH THE TENANT SEPERATION WALLS |
| | AND THE MAIN ELECTRIC ROOM WALLS ARE A 1 HR FIRE RATED |
| | ASSEMBLY, PLEASE PROVIDE FIRE RATING OF THE TWO DOORS |
| | WITHIN THE EXIT VESTIBULE FBC-B TABLE 715.4. |
| | |
| | 4) THE EXIT VESTIBULE MAY REQUIRE EXIT LIGHTING, THE |
| | PLANS DO NOT SHOW ANY WINDOWS IN THIS ROOM FBC-B |
| | 10062.1(2). |
| | |
| | 5) 712.6 FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, |
| | SMOKE BARRIERS AND SMOKE PARTITIONS OR ANY OTHER WALL |
| | REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE |
| | EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR |
| | STENCILING IN A MANNER ACCEPTABLE TO THE AUTHORITY |
| | HAVING JURISDICTION. SUCH IDENTIFICATION SHALL BE ABOVE |
| | ANY DECORATIVE CEILING AND IN CONCEALED SPACES. |
| | SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS: "FIRE |
| | AND SMOKE BARRIER - PROTECT ALL OPENINGS." |
| | |