| 2011-06-06 14:00:27 | BUILDING REVIEW APPROVED WITH PROVISO: |
| | 1- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9B-72 FOR: A) FLAT ROOF. IDENTIFY SPECIFIC |
| | APPROVED ASSEMBLY TO BE INSTALLED. AND, PROVIDE RAS 117 |
| | CALCULATIONS AS REQUIRED BY GENERAL LIMITATION #7. |
| | B) SLIDING GLASS DOORS. NOA 09-0324.16 SUBMITTED WAS |
| | SUPERSEDED BY MIAMI-DADE WEBSITE. PROVIDE CURRENT NOA. |
| | C) GLASS BLOCK. NOA 07-0626.10 SUBMITTED IS FOR SMALL |
| | MISSILE IMPACT. NEED LARGE MISSILE IMPACT PROTECTION. |
| | SEC. R301.2.1.2. |
| | D) SINGLE HUNG WINDOW EGRESS WINDOW. |
| | |
| | 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC. |
| | |
| | 3- REVISE ENERGY CALCULATIONS: ROOF MATERIAL SPECIFIED |
| | ON PAGE 2 DOESN'T MATCH PLANS. |
| | |
| | 4- SHEET 1 OF 6: A) REVISE DOORS & WINDOWS DESIGN |
| | PRESSURES TO CORRESPOND TO EXPOSURE "C". |
| | B) UPDATE GENERAL NOTES #7 AND #12. SEE THE 2007 |
| | FLORIDA RESIDENTIAL CODE FOR CORRECT CODE SECTION. |
| | C) UPDATE WIND INFORMATION: * REVISE ALL NOTES CITING |
| | CORRESPONDING SECTIONS OF THE 2007 FLORIDA RESIDENTIAL |
| | CODE. ** UPDATE LAST NOTE: THERE IS NOT 2004 FBC. |
| | |
| | 5- SPECIFY SIZE OF EGRESS WINDOW ON EXISTING BEDROOM TO |
| | VERIFY COMPLIANCE WITH SEC. R310. |
| | |
| | 6- SHEET 4 OF 6: A) PROVIDE COMPLETE SECTION/DETAILS |
| | FOR NEW INTERIOR BEARING WALLS. SPECIFY ALL CONNECTORS |
| | TOP/BOTTOM. SEC. 106.1.2 CITY AMENDMENTS TO FBC. |
| | B) REVISE FLORIDA PRODUCT APPROVALS NUMBERS SPECIFIED |
| | ON THE STRAPPING SCHEDULE. NUMBERS SHOWN ARE NOT |
| | CURRENT. |
| | |
| | 7- SHEET 5 OF 6 TYPICAL WALL SECTION: * SPECIFY SIZE OF |
| | CONTINUOUS VENTILATION TO VERIFY COMPLIANCE WITH SEC. |
| | R806. **STUCCO CAN'T BE 6" BELOW GRADE. SEC. R704.1. |
| | |
| | 8- SURVEY NEEDS TO HAVE SURVEYOR'S ORIGINAL SEAL & |
| | SIGNATURE AS REQUIRED BY CHAPTER 472 FLORIDA STATUTE. |