| 2011-04-27 15:57:30 | RESIDENTIAL (R3) ADDITION, MECHANICAL REVIEW CHECKLIST. | | | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. | | | | | | 1- DRAWINGS SUBMITTED ARE TOO DARK. THEY ARE NOT | | | SUITABLE FOR SCANNING IN THE FILE NET FILE SYSTEM FOR | | | PUBLIC RECORDS. SEC. 106.1.3 CITY AMENDMENTS TO FBC. | | | NEED TO PROVIDE CLEAR LEGIBLE DRAWINGS. | | | | | | 2- A) A/C CONTRACTOR TO PROVIDE HIS/HER CONTRACTOR'S | | | LICENSE # AND SIGN THE MECHANICAL DRAWINGS. | | | B) CONTRACTOR TO SPECIFY ALL EQUIPMENT INFORMATION ON | | | PLANS. | | | | | | 3- DUCTWORK IS LOCATED ON THE FLAT ROOF. CLARIFY HOW IS | | | THE ROOF GOING TO BE INSULATED IF THE DUCTWORK DOESN'T | | | ALLOW INSULATION INSTALLATION?. COORDINATE WITH | | | ARCHITECTURAL AND STRUCTURAL DRAWINGS AND | | | SPECIFICATIONS. | | | | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 | | | |
|