2011-04-11 10:43:59LOCATE EXISTING SERVICE, MAIN DISCONNECTS AND PANELS ON
 THE ELECTRIC FLOOR PLAN. NEC 110.26
 THE MAIN ELECTRICAL DISCONNECTS MUST BE GROUPED
 TOGETHER IN ONE LOCATION. NEC 230.70, 230.71
 RECEPTACLES SHALL BE TAMPER RESISTANT. NEC 406.11
 PROVIDE AN INTERSYSTEM BONDING STRIP AT THE SERVICE
 GROUND. NEC 250.94
  