Plan Review Notes
Plan Review Notes For Permit 11040116
Permit Number 11040116
Review Stop B
Sequence Number 1
Notes
Date Text
2011-04-27 15:59:43RESIDENTIAL (R3) ADDITION, BUILDING REVIEW CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FL. ST..
 ***NOTE: THIS MAY BE RECORDED LATER AT TIME OF PERMIT
 PICK UP.
  
 2- AFTER PLANS ARE REVISED BRING THEM TO PALM BEACH
 COUNTY (2300 N JOG RD) TO VERIFY IF IMPACT FEES ARE
 DUE. BRING BACK STAMPED PLANS AND COPY OF THE PAID
 RECEIPT IF FEES ARE DUE.
  
 3- PERMIT VALUATION DECLARED IN THE PERMIT APPLICATION
 IS TOO LOW. SEC. 108.3 CITY AMENDMENTS TO FBC.
 VALUATION WAS UPDATED TO $121.325 USING THE ICC
 BUILDING VALUATION DATA. PERMIT VALUATION TO INCLUDE
 ALL PROFESSIONAL DESIGN FEES, LABOR AND MATERIALS AND
 CONTRACTOR'S OVERHEAD AND PROFIT. TOTAL PERMIT FEE
 VALUE IS $3584.70.
  
 4- MINIMUM FLAT ROOF SLOPE IS 1/4" PER FT. SEC.
 R905.11.1 OF 2007 FLORIDA RESIDENTIAL CODE. SLOPE
 SPECIFIED ON RIGHT ELEVATION ON SHEET 1 OF 6 IS 1" PER
 10'. REVISE AS REQUIRED AND SPECIFY SLOPE ON THE ROOF
 FRAMING PLAN ALSO.
  
 5- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) FLAT ROOF. * NOA 08-0204.08 SUBMITTED IS FOR
 CEMENTITIOUS WOOD FIBER DECKS. NEED ONE FOR WOOD DECKS.
 ** CLEARLY INDICATE WHICH APPROVED ASSEMBLY IS GOING TO
 BE INSTALLED. INSULATED OR NON-INSULATED ASSEMBLY. ***
 IF USING INSULATED SYSTEM, THEN SPECIFY HOW ACHIEVING
 THE R-30 VALUE REQUIRED BY THE ENERGY CALCULATIONS.
 **** PROVIDE RAS 117 CALCULATIONS AS REQUIRED BY
 GENERAL LIMITATION #7. CHECK ON NOA IF CALCULATIONS
 NEED TO BE SIGNED AND SEALED.
  
 B) SLIDING GLASS DOORS. NOA 09-0324.16 SUBMITTED WAS
 SUPERSEDED BY MIAMI-DADE WEBSITE. PROVIDE CURRENT NOA.
  
 C) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. OR, SPECIFY FLORIDA PRODUCT APPROVAL OR
 NOA NUMBER ON PLANS.
  
 6- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC.
  
 7- ENERGY CALCULATIONS SUBMITTED:
 A) ROOF MATERIAL SPECIFIED ON PAGE 2 DOESN'T MATCH ROOF
 MATERIAL SPECIFIED ON PLANS AND PRODUCT APPROVAL.
  
 B) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM.
  
 8- PROVIDE OPENING FRAMING DETAILS FOR NEW SKYLIGHT.
 SEC. 106.1.1 CITY AMENDMENTS TO FBC.
  
 9- SPECIFY THE FOOTING SIZES FOR THE INTERIOR BEARING
 WALLS. SEC. 106.1.1 CITY AMENDMENTS.
  
 10- ENERGY CALCULATIONS ARE TAKING THE CEILING FAN
 CREDIT. SPECIFY ON PLANS CEILING SIZE ON ALL ROOMS
 REQUIRED BY SEC. C4.2.1.1 AND TABLE C4.2.1.1.
  
 11- PROVIDE DETAIL/SPECIFICATIONS SHOWING HOW PROVIDING
 THE R-30 INSULATION ON THE CEILING AREAS WHERE THE A/C
 DUCTWORK IS RUNNING. SEC. 106.1.1 CITY AMENDMENTS.
  
 12- PROVIDE COMPLETE SECTIONS/DETAILS/SPECIFICATIONS
 SHOWING HOW THE WINDOWS ARE ATTACHED TO THE GLASS
 BLOCK. IN THE BEDROOM AREA. SEC. 106.1.1 CITY
 AMENDMENTS TO FBC.
  
 13- SHEET 1 OF 6: A) REVISE BUILDING CODE SPECIFIED
 UNDER THE DESIGN PRESSURES TABLE. CURRENT CODE IS THE
 2007 FLORIDA RESIDENTIAL CODE NOT 2001 FBC.
  
 B) UPDATE GENERAL NOTES #5(B), #7 AND #12. REFER TO THE
 2007 FLORIDA RESIDENTIAL CODE FOR CORRECT CODE SECTION.
  
 C) UPDATE WIND INFORMATION: * REFER TO 2007 FLORIDA
 RESIDENTIAL CODE. REVISE ALL NOTES CITING CORRESPONDING
 SECTIONS OF THE 2007 FLORIDA RESIDENTIAL CODE. **
 CLARIFY AND COORDINATE EXPOSURE CATEGORY. UPLIFT
 WORKSHEET SPECIFIES EXPOSURE "B" WHILE WIND INFORMATION
 SPECIFIES EXPOSURE "C". *** SHEARWALLS: PLANS TO
 IDENTIFY ALL SHEARWALLS THAT COMPLY WITH THE
 SPECIFICATIONS WRITTEN ON THIS ITEM. ****UPDATE LAST
 NOTE: THERE IS NOT 2004 FBC.
  
 14- SHEET 2 OF 6: IDENTIFY ROOM ON EXISTING HOUSE WHOSE
 WINDOWS ARE BEING CLOSED. IF IT'S A BEDROOM, THEN I
 NEED TO VERIFY COMPLIANCE WITH THE EGRESS REQUIREMENTS
 WHEN THE WINDOWS ARE CLOSED OFF.
  
 15- SHEET 4 OF 6: A) REVISE FLORIDA PRODUCT APPROVALS
 NUMBERS SPECIFIED ON THE STRAPPING SCHEDULE. NUMBERS
 SHOWN ARE NOT CURRENT.
  
 B) REVISE NOTE #9. SEE SIMPSON CATALOG FOR CORRECT NAIL
 TYPE TO BE USED. OTHERWISE, PROVIDE ENGINEERING
 ANALYSIS TO SHOW COMPLIANCE WITH THE CALCULATED LOADS.
  
 C) SPECIFY CONNECTORS AT THE ENDS OF (2)2X12 HEADER BY
 THE FAMILY AREA. AND CONNECTORS AT THE BOTTOM OF (2)2X4
 SUPPORTING THE HEADER TO VERIFY COMPLIANCE WITH THE
 UPLIFT LOADS.
  
 D) SPECIFY CONNECTORS FOR THE SHORT FRAMING MEMBERS AT
 THE NEW PATIO ROOF ( SEE WEST SIDE) AND AT THE MAIN
 ROOF (SEE EAST SIDE).
  
 16- SHEET 5 OF 6: A) SHOWER SECTION TO SPECIFY
 REINFORCEMENT AT THE THICKENED EDGE.
  
 B) REVISE DOOR BUCK DETAIL. NEED TO SPECIFY BUCK SIZE
 THAT PROVIDE FULL SUPPORT TO THE DOOR FRAME. SEE
 PRODUCT APPROVAL FOR FRAME SIZE. SEC. R613.6.
  
 C) REVISE WINDOW BUCK DETAIL. BEVELED BUCKS ARE NOT
 ALLOWED. NEED TO PROVIDE FULL SUPPORT TO THE WINDOW
 FRAME. SEC. R613.6.
  
 D) TYPICAL WALL SECTION: * ROOF SHEATHING NAILS TO BE
 RING SHANK NAILS. SEC. R803.2.3.1. ** SPECIFY SIZE OF
 CONTINUOUS VENTILATION TO VERIFY COMPLIANCE WITH SEC.
 R806.
 *** CLARIFY FOOTING AND FINISH GRADE. DRAWING IS NOT
 CLEAR HOW GETTING THE 12" BELOW GRADE. CLARIFY SIZE OF
 FOOTING. BOTTOM OF SIDING MATERIAL TO BOTTOM OF FOOTING
 IS 16"?. WHAT'S THE SIDING MATERIAL?. SEE ELEVATIONS
 FOR EXTERIOR FINISH.
  
 17- SURVEY NEEDS TO HAVE SURVEYOR'S ORIGINAL SEAL AND
 SIGNATURE AS REQUIRED BY CHAPTER 472 FLORIDA STATUTE.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712