| 2011-04-21 16:02:34 | 2223 PALM BEACH LAKES BOULEVARD |
| | PERMIT #11040096 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | THE ADDRESS IN THE TITLEBLOCK STILL DOES NOT MATCH |
| | PERMIT APPLICATION. |
| | |
| | THE AMOUNT AND LOCATION OF EXIT DOORS DOES NOT MATCH |
| | THE FIELD CONDITIONS. EXIT DOORS DO NOT EXIST ON THE |
| | WEST SIDE OF THE BUILDING. |
| | |
| | FOR ISSUANCE OF A GENERAL BUILDING PERMIT, THE FLORIDA |
| | BUILDING CODE REQUIRES FIRE PROTECTION CONSTRUCTION |
| | DOCUMENTS FOR THE DESIGN OR ALTERATION OF AUTOMATIC |
| | FIRE SPRINKLERS. |
| | |
| | THE NUMBER OF FIRE ALARM NOTIFICATION APPLIANCES AND |
| | EMERGENCY LIGHT FIXTURES APPEAR TO BE INADEQUATE FOR |
| | THIS SIZE SPACE. |
| | |
| | SEPARATE PLANS AND PERMITS REQUIRED FOR INSTALLATION OR |
| | MODIFICATION OF THE FIRE ALARM AND FIRE SPRINKLER |
| | SYSTEM. |
| | |
| | INDICATE ON PLANS IF THIS BUILDING FUNCTIONS AS A MIXED |
| | NONSEPARATED OCCUPANCY OR AS A SEPARATED OCCUPANCY. |
| | |
| | EACH NEW SMOKE OR FIRE-RATED WALL/PARTITION SHALL BE |
| | PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING |
| | FIRE SMOKE BARRIER PROTECT ALL OPENINGS. CHARACTERS |
| | SHALL BE AT LEAST 4 INCHES IN HEIGHT AND HALF INCH IN |
| | WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 |
| | FEET ON CENTER. |
| | |
| | PENETRATIONS THROUGH A FIRE RATED WALL ASSEMBLY SHALL |
| | BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE. |
| | |
| | |
| | WESLEY JOLIN |
| | WEST PALM BEACH FIRE RESCUE |
| | FIRE & LIFE SAFETY PLAN REVIEW |