| Plan Review Notes For Permit 11040096 |
| Permit Number |
11040096 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-04-07 13:32:09 | 2231 PALM BEACH LAKES BOULEVARD, SUITE #103 | | | PERMIT #11040096 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | VERIFY THE BUILDING ADDRESS IS CORRECT. THE ADDRESS | | | ASSOCIATED WITH THIS PCN IS 2223 PALM BEACH LAKES | | | BOULEVARD. | | | | | | DESIGN SHALL CONFORM TO THE FLORIDA FIRE PREVENTION | | | CODE 2007 EDITION NFPA 1 AND NFPA 101, 2006 EDITION | | | WITH FLORIDA AMENDMENTS. | | | | | | PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY | | | RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING | | | NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM | | | WWW.KNOXBOX.COM. | | | | | | THE TENANT DEMISING WALL IS INCORRECTLY LABLED AS | | | EXTERIOR MASONRY BLOCK WALL. | | | | | | ONLY ONE FIRE ALARM DEVICE IS SHOWN AND IS GENERICALLY | | | LABLED AS FIRE ALARM. | | | | | | THE REFERENCE TO CHAPTER 10 OF THE LIFE SAFETY CODE IS | | | NOT THE MERCANTILE OCCUPANCY CHAPTER. | | | | | | THE OCCUPANT LOAD FACTOR FOR STREET FLOOR MERCANTILE | | | OCCUPANCIES IS NOT 40 SQUARE FEET PER PERSON. | | | | | | IN ORDER TO PERFORM A THOROUGH PLAN REVIEW, ADDITIONAL | | | INFORMATION IS REQUIRED SUCH AS FURNITURE LAYOUT, NEW | | | AND EXISTING FIRE ALARM INITIATION/NOTIFICATION | | | APPLIANCES, HEIGHT OF STORAGE, LOCATION OF EXISTING | | | FIRE EXTINGUISHER, EXISTING EXIT SIGN LOCATIONS AND | | | EMERGENCY LIGHTING ETC. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW | | | | | | | | | | | | | | | |
|